Page 7 of 67
SK2018 CHV2-V/P-ECM-001
4-Pipe Systems
Product range: CHV2 Coanda Effect Hydronic unit 4-pipe with EC motor and 1 row Auxiliary Heating Coil
CHV2-[Size]-P~ECM
1
2
3
Unit
Configuration
Configuration
4-pipe
Number Of Fan Blowers
Single
Twin
Power Supply
(V/Ph/Hz)
230 / 1 / 50
220 / 1 / 60
Operation Control
~S: Complete function on board PCB with integrated group control functionality
~W: Flexible function on board PCB with drain pump and zone control functionality
Air
Total
Air Flow
H
m
3
/h
287
365
524
M
220
288
373
L
150
230
290
C
o
o
lin
g
Cooling Capacity
e
H
kW
1.64
2.07
3.03
M
1.26
1.73
2.36
L
0.98
1.5
1.99
Sensible Cooling
Capacity
e
H
1.17
1.46
2.13
M
0.88
1.21
1.63
L
0.67
1.04
1.36
Latent Cooling Capacity
H
0.47
0.61
0.9
M
0.38
0.52
0.73
L
0.31
0.46
0.63
FCEER
e
Rating
94.37
143.92
173.63
Class
C
B
B
H
e
at
in
g
Heating Capacity
e
H
kW
1.35
1.88
2.53
M
1.11
1.58
1.97
L
0.83
1.34
1.61
FCCOP
e
Rating
144.69
237.83
244.2
Class
C
B
B
Sound
Sound Power Level ( Outlet )
e
49/43/39
45/42/36
53/44/37
El
e
ct
ri
ca
l
Power input in cooling
mode
e
H
W
25
20
28
M
14
12
15
L
10
10
10
Power input in heating
mode
e
H
W
20
15
23
M
9
7
10
L
5
5
5
H
yd
ra
u
lic
Cooling Water Flow
Rate
H
L/h
281
355
520
M
217
296
404
L
167
257
341
Cooling Pressure Drop
e
H
kPa
12.7
10.8
22.4
M
8.1
7.9
14.6
L
5.3
6.2
10.9
Heating Water Flow
Rate
H
L/h
115
161
217
M
96
136
169
L
71
115
138
Heating Pressure Drop
e
H
kPa
5
12.5
19.7
M
3.6
9.3
12.8
L
2.2
7
9.2
Water Content ( at 1 row Auxiliary
Heating Coil)
L
0.073
0.116
0.164
Construction
and
Packing Data
Water
Connections
Type
Socket (Threaded Female)
in
mm[in.]
DN15 [1/2]
out
Condensate Drainage Connection
25.4 [1]
Dimensions
L
mm
567
867
1167
W
560
560
560
H
265
265
265
Panel Dimensions
595*595*12
895*595*12
1195*595*12
Net Weight
kg
21
31
37
"e": Above specifications are based on declared Eurovent test data for the year of publication of this document. To confirm the most updated
specifications, please visit www.eurovent-certification.com.
Eurovent testing conditions:
a. Cooling mode (4-pipe):
b. Heating mode (4-pipe):
- Return air temperature: 27C DB/ 19C WB.
- Return air temperature: 20C
- Inlet/ outlet water temperature: 7C/ 12C.
- Inlet/ outlet water temperature: 65C/55C