SK2018 CHV2-V/P-ECM-001
LED Display and Error Description
LED receiver in ABS housing with 0.5m (SGS14HFCA-01010101) or 1.8m (SGS14HFCA-01010102) pre-wiring.
Flexible Control PCB - W Control Type
Fan speed setting
LED indication
Condition
High speed
Red LED On
Normal
Medium speed
Yellow LED On
Normal
Low speed
Green LED On
Normal
For all units - Green LED blinks
Item
Blink
Reason
Remedy
Indoor coil sensor 1 failure
Green LED blinks 4 times,
stops for 3s
Ti1 sensor connection
is damaged.
1.
Check if Ti1 plug is
connected or not.
2.
Check sensor’s resistor is
good or not.
Water pump failure
Green LED blinks 7 times,
stops for 3s
Float switch is opened.
1.
Check if the condensate
water pipe is connected
or not.
2.
Check if the pump is
functioning or not.
EC motor failure
Green LED blinks 9 times,
stops for 3s
No EC motor feedback
1.
Check DIPB-SW5 and
SW6 setting.
2.
Check the EC motor
Anti-frozen protection
Green LED blinks 11
times, stops for 3s
When unit is standby,
Ti1<2ºC
Turns on unit to keep Ti
higher than 5ºC.