10 

   

 

Ø

 

EN61000-2-2 (immunity to low frequency signals) 

 

6 K R L  

 

Ø

 

Safety: EN62040-1-1:2003 

Ø

 

Conducted emission: EN50091-2 

Ø

 

Rated output current exceeding 25A limits 

Ø

 

Radiated emission: EN50091-2 

Ø

 

Rated output current exceeding 25A limits 

 

EMS 

EN61000-4-2(ESD) 

Level 4 

 

EN61000-4-3(RS) 

Level 3 

 

EN61000-4-4(EFT) 

Level 4 

 

EN61000-4-5(lighting surge) 

Level 4 

 

Ø

 

EN61000-2-2 (immunity to low frequency signals) 

 

5.5. Communication port 

 

The  type  of  signals,  serial  command  (RS232),  is  provided  by  the  UPS  to  communicate  with  a  host 

computer. The RS232 communication port transmits both utility power and UPS status to the host computer, 
providing the host computer with proprietary command sequence to monitor the utility power and UPS status 
and to control the UPS output. 
 

The data format of RS232 is listed as followed: 

 

Baud rate 

2400 bps 

Data length 

8 bits 

Ending bit 

1 bit 

Parity bit 

None 

 
5.5.1. RS232 interface 
 

Two types of signals, relay contact or serial command (RS232), are provided by the UPS to communicate 

with a host computer. The relay contact transmits both utility power and UPS status to the host computer by 
using 

ON

 and 

OFF

 states of relays, providing the host computer with proprietary command sequence to 

monitor the utility power and UPS status and to control the UPS output. The host computer can also monitor 
the UPS through RS232 communication port. 
 

Pin# 

Description 

I/O 

TXD 

Output 

RXD 

Input 

GND 

Input 

 
 
 
 
 
 
 
 
 

 
 

 

RS232 interface 

 
5.5.2. AS400 interface 
 

PDF 

文件使用

 "pdfFactory Pro" 

试用版本创建

 

www.fineprint.cn

Summary of Contents for 1KRS

Page 1: ...1 H series array online UPS 1 6KRS L U U Us s se e er r r s s s m m ma a an n nu u ua a al l l PDF pdfFactory Pro www fineprint cn...

Page 2: ...2 Rear panel 5 4 Maintenance 7 4 1 Operation environment 7 4 2 Battery application 7 4 3 Trouble shooting 7 5 Technical data 8 5 1 Electrical specifications 8 5 2 Typical stored energy time 8 5 3 Mech...

Page 3: ...quipment which would overload the UPS system e g laser printers to the UPS output socket Place cables in such a way that no one can step on or trip over them Do not connect domestic appliances such as...

Page 4: ...s voltages may occur between the battery terminals and the ground Before touching any operation please verify that no voltage is present Batteries may cause electric shock and have a high short circui...

Page 5: ...e mains power via the bypass Alarm LED Lights up when the UPS system is in fault condition at the same time an acoustic warning signal is issued every second Indicator Load level signaled when the AC...

Page 6: ...6 1KRL 2KRL 3KRL PDF pdfFactory Pro www fineprint cn...

Page 7: ...lable wiring can be completed by professional electrician Note terminal cover should be put back for safety reason after wiring completed Input breaker if the breaker pops out off reduce the load on t...

Page 8: ...ration to the UPS for long time then the battery must be charged every three month 4 3 Trouble shooting Using the table below some common problems can be solved If the problem still exists or some pro...

Page 9: ...at 25 C in minutes Model 100 load 50 load 1K 5 14 2K 9 21 3K 5 15 6K 8 23 5 3 Mechanical data Model Net weight Kg Dimension mm 1KS 16 3 1KL 9 1 Battery pack 36V 22 5 2KL 11 5 3KL 12 3 Depth 450 Batter...

Page 10: ...proprietary command sequence to monitor the utility power and UPS status and to control the UPS output The data format of RS232 is listed as followed Baud rate 2400 bps Data length 8 bits Ending bit 1...