name value range description
default
43
special (-25...90 mV scaling necessary
r
page 36)
44
special (-500...500 mV scaling necessary
r
page 36)
45
special (-5...5 V scaling necessary
r
page 36)
50
potentiometer 0...160 Ohm
51
potentiometer 0...450 Ohm
52
potentiometer 0...1600 Ohm
S.Lin
linearization only adjustable with
S.tYP
: 18, 23, 24, 30, 40 ... 45
0
0
none
1
Speciallinearization
EditingthelinearizationtablewithBlueControl(engineeringtool)is
possible.ThecharacteristicforKTY11-6temperaturesensorsisfactory-set.
Corr
measurement value correction / scaling
0
0
no correction
1
offset-correction (in
CAL
- level)
2
2-point-correction (in
CAL
- level)
3
scaling (in
PArA
- level)
fAI1
forcing INP
(only visible with BlueControl!)
0
0
no forcing
1
forcing via interface
Lim
name value range description
default
Fnc.1
Fnc.2
Fnc.3
function of limit 1 (2, 3)
1
0
switched off
1
measured value monitoring
2
measured value moni storing of alarm status.
A stored limit value can be set back via error list or digital input or
è
-key (
→
LOGI
/
Err.r
).
3
signal change
4
signal storing of alarm status.
A stored limit value can be set back via error list or digital input or
è
-key (
→
LOGI
/
Err.r
).
Src.1
Src.2
Src.3
source for limit value 1 (2, 3)
0
0
process value = absolut alarm
1
control deviation Xw (processvalue - set-point) = relative alarm
2
control deviation Xw (=relative alarm) with suppression at start
and with set-point change
3
measured value INP
6
set-point
7
y (controller output)
Hour
OFF..999999
operating hours
(only visible with BlueControl!)
OFF
Swit
OFF..999999
operation cycle number
(only visible with BlueControl!)
OFF
Out.1
und
Out.2
name
value range description
default
O.Act
circuit direction of output OUT1
0
0
direct / open circuit principle
1
inverse / closed circuit priciple
Configuration level
Digital 280-1
Configuration
25