The control parameters can be determined from the values calculated for delay
time T
u
, maximum rate of increase v
max
, control range X
h
and characteristic K
according to the
formulas
given below. Increase Xp, if line-out to the set-point
oscillates.
Controller
Digital 280-1
Manual tuning
21
y
= correcting variable
Y
h
= control range
Tu
= delay time (s)
Tg
= recovery time (s)
X
max
= maximum process value
V
max
=
Xmax
Tg
=
{
{
x
t
=
max. rate of
increase of process value
Parameter adjustment effects
Parameter
Control
Line-out of disturbances
Start-up behaviour
Pb1
higher increased damping slower line-out
slower reduction of duty cycle
lower reduced damping
faster line-out
faster reduction of duty cycle
td1
higher reduced damping
faster response to disturbances faster reduction of duty cycle
lower increased damping slower response to disturbances slower reduction of duty cycle
ti1
higher increased damping slower line-out
slower reduction of duty cycle
lower reduced damping
faster line-out
faster reduction of duty cycle
Formulas
K = Vmax * Tu
controller behavior Pb1 [phy. units]
td1 [s]
ti1 [s]
With 2-point and
3-point controllers,
the cycle time must
be adjusted to
t1 / t2 £ 0,25 * Tu
PID
1,7 * K
2 * Tu
2 * Tu
PD
0,5 * K
Tu
OFF
PI
2,6 * K
OFF
6 * Tu
P
K
OFF
OFF
3-point-stepping
1,7 * K
Tu
2 * Tu
Tu
Tg
t
x
y
100%
0%
t
Yh
Xmax
{
X
{
t