5.2.6
CONTR (FB no.: 50 ... 57 Type no.: 91)
All data which concern the controller are grouped in function block ‘CONTR’. They are available once for
each controller channel.
Process data
General
(function no.: 0)
Code Descr.
R/W
Type
Description
Range
Rem.
00
Block
R
Block
Block access (1...9)
1
Status 1
R
ST1
Status 1
A
3
W
R
FP
Eff. set-point
4
X
R
FP
Eff. process value
5
Y
R
FP
Effective output value
6
xw
R
FP
Control deviation
13
Status Alarm x R
INT
Status x and Alarm x
B1
18
Type
R
INT
Type no. of function block
90
20
Block
R
Block
Block access (21...26)
21
Xeff
R
FP
Eff. process value
22
Yeff
R
FP
Effective output variable
23
HC
R
FP
Heating current measureement value
24
Unit_State
R
ICMP
Input values (di)
Ä
page 12
25
Alarm_x
R
ICMP
Alarm values
Ä
page 13
B2
26
Status_x
R
ICMP
Status information
Ä
page 13
30
Block
R
Block
Block access (31...38)
33
A/M
R/W
INT
Automatic/manual switch-over
0..1
34
OStart
R/W
INT
Optimization start
0..1
35
We/i
R/W
INT
Wext/Wint switch-over
0..1
36
w/w2
R/W
INT
w/w2 switch-over
0..1
38
Coff
R/W
INT
Controller off/on
0..1
C
Rem. A Status1: (code 01)
MSB
LSB
D7
D6
D5
D4
D3
D2
D1
D0
Bit no.
Name
Allocation
Status ‘0’
Status ‘1’
D0
Y1
Switching output
off
on
D1
Y2
Switching output
off
on
D2
A/M
Auto/manual
auto
manual
D3
CFail
Controller status
ok
not ok
D4
Coff
Controller switched off
no
yes
D5
XFail
Sensor fail
no
yes
D6
‘1’
always ‘1’
D7
Parity
Rem. B1 Status_alarm_x: Code 13
MSB
LSB
D15 D14 D13 D12 D11 D10 D9 D8 D7 D6 D5 D4
D3 D2 D1 D0
Bit no.
Name
Allocation
Status ‘0’
Status ‘1’
D0
w/w2
w/w2 switch over
w
w2
D1
we/wi
extern/intern switch over
extern
intern
D2
w/wanf
Start-setpoint switch over
w
wanf
D3
Orun
Optimisation activ
no
yes
D4
A/M
Automatic/Manuel switch over
Auto
Man
D5
Coff
Controller off
no
yes
D6
Y1
Switchung output 1
off
on
D7
Y2
Switching output 2
off
on
D8
Lim HH
Alarm HH
off
on
D9
Lim H
Alarm H
off
on
D10
Lim L
Alarm L
off
on
D11
Lim LL
Alarm LL
off
on
D12
Fail
Alarm sensor fail
no
yes
D13
HCAl
Heating current alarm
off
on
D14
LoopAl
Loop alarm
off
on
D15
"0"
always "0"
Function block protocol
37
9499 040 50511