14 

 

8.7

 

Assembling sensors of thermostat 
2 and 3 

After  connecting  two  additional  temperature 
sensors,  the  ecoSTER200  room  panel 
provides independent temperature regulation 
in  three  rooms.  Regulator  cooperates  with 
CT7  type  room  temperature  sensors.  Use  a 
cable  with  a  cross-section  of  at  least  0.25 
mm

2

  to  connect  sensors.  Recommended 

cross-section  is  0.5  mm

2

.  Cable  should  not 

be  longer  than  20  m.  Sensor  cables  should 
be separated from power  cables (~230V). If 
not,  incorrect  temperature  readings  can 
occur.  Minimum  distance  between  sensor 
cables  and  power  cables  should  be  at  least 
10 cm. 

In order to guarantee  a maximum operation 
efficiency  of  the  regulator,  follow  the 
recommendations  concerning  a  place  of 
sensor assembly: 

1.

 

Sensors  should  be  assembled  on  a 

height app. 1.5 m over the floor level. 

2.

 

Avoid places which are strongly sunlit, 

close  to  heating  devices,  in  direct 
vicinity  of  doors  and  windows,  where 
a temperature measurement could be 
easily 

interfered 

by 

external 

conditions. 

3.

 

Avoid places with weak air circulation, 

e.g.: behind furniture. 

 

 

 
Fig. 8.1

1

 Diagram of cooperation between ecoSTER200 and ecoMAX, where: 1 - ecoSTER200, 2 - 

room sensor of thermostat 2 type CT7, 3 - room sensor of thermostat 3 type CT7, 4 

 module B 

(extends 

the 

system 

by 

heat 

circulations), 

ecoMAX 

controller

 

1

 Diagram does not replace a project of installation and can be used only for reference. 

Summary of Contents for ecoSTER 200

Page 1: ...Room panel ecoSTER 200 HARDWARE VERSION 2 FOR ECOMAX CONTROLLERS OPERATION AND MAINTENANCE MANUAL ISSUE_EN 1 1 APPLICABLE TO SOFTWARE v10 XX XXX 11 2015...

Page 2: ......

Page 3: ...U 8 7 11 SETTINGS 8 7 11 1 Weather sensor 8 7 11 2 Thermostat settings 9 7 11 3 Hysteresis 9 7 11 4 Temperature correction 9 7 11 5 Language change 9 7 11 6 Sound alarm 9 7 11 7 Clock settings 9 7 11...

Page 4: ...trol It can be used in household and similar facilities as well as in slightly industrialized facilities 3 Information about documentation The ecoSTER200 room panel manual is a supplement for the corr...

Page 5: ...l operation is easy and intuitive When the panel displays main window turn the button right or left in order to change displayed main window 1 thermostat 2 thermostat 3 boiler If temperature sensors o...

Page 6: ...ration and confirming by pushing the button the Output operation mode is activated in this mode the economic temperature is set to a preset duration Note Time will be counted by full hours It means th...

Page 7: ...a duration of 14 days a real duration of the Holiday mode will be 13 days 6 hours and 15 minutes When a preset time elapses the regulator switches to a previous mode In the main window in a place for...

Page 8: ...temperature is set in MENU Temperature settings Day temperature Preset anti freeze temperature is set in MENU Temperature settings Anti freeze temperature 7 10 ecoMAX boiler regulator menu In order t...

Page 9: ...der to set time and date select MENU Settings Clock According to set date the device will automatically set an appropriate weekday The ecoSTER200 panel is equipped with a system clock which is indepen...

Page 10: ...bear any responsibility for damages caused by failure to observe this manual 8 5 Instructions for assembly Open the casing as shown on the figure below Drill holes in a wall If a wall is made of brick...

Page 11: ...tton on this terminal with a flat screwdriver inserting the cable and releasing the button Below are the wiring scheme thermostats with room sensors 2 and 3 type CT7 and the way VCC panel power module...

Page 12: ...12 8 6 2 Connection to ecoMAXX800 R3 T3 and ecoMAX800 P3 D3 8 6 3 Connection to ecoMAX850 P1...

Page 13: ...13 8 6 4 Connection to ecoMAX850 P2 R2 D2 8 6 5 Connection to ecoMAX860 P1 P2 D1 D2...

Page 14: ...In order to guarantee a maximum operation efficiency of the regulator follow the recommendations concerning a place of sensor assembly 1 Sensors should be assembled on a height app 1 5 m over the floo...

Page 15: ......

Page 16: ...ul Wsp lna 19 Ignatki 16 001 Kleosin Poland phone 48 85 749 70 00 fax 48 85 749 70 14 plum plum pl www plum pl www plumelectronics eu...

Reviews: