7077-801F • 08/20
32
F. Through The Wall
Horizontal termination cap must be a minimum of 6
inches. (152mm) from the wall. Approved for mobile home
installations. Must use 3 or 4 inch (76-102mm) “L” or “PL”
listed pellet venting or Listed double wall pipe and an
authorized Outside Air Kit in mobile homes.
NOTE:
In Canada, where passage through a wall or
partition of combustible construction is desired, the
installation shall conform to
CAN/CSA-B365
NOTICE:
Please note that while the minimum clearance
for the termination cap is 6 inches (152mm) there is the
possibly of soot build-up around the termination area. If
this occurs we suggest to move the termination further
away from the house to prevent it. The suggested
minimum is 12 inches.
DO NOT DOWNWARD VENT.
The following will occur:
•
The appliance will not vent properly
•
Smoke spillage in the house
•
Excessive sooting
CAUTION
!
6 in.
(152mm)
Minimum
Non-combustible Hearth Pad
Wall
Thimble
Horizontal
Termination
Cap
2 in.
(50.8mm)
Minimum
6 in.
(152mm)
Minimum
From Glass
Straight Out
Wall
Thimble
Illustration shows venting going in both directions.
Choose which one is best for your installation.
3 in. (76mm)
Minimum
3 in.
(76mm)
Minimum
6 in (152mm) Minimum
6 in (152mm)
Minimum
45 Degrees