POWER REQUIREMENTS
MODEL
PLATINUM ll
VOLTS
240
AMPS
50
AMP
LOAD
40
MARKING
3 Wire #6 + Grd 3
APPLICATION
HS200VS
Load 120 Volts (Black)
To Spa
Load 120 Volts (Red)
To Spa
Load Neutral (White)
To Spa
IMPORTANT
6 Gauge Copper Wire Must
Be Used
Pig Tail (White)
From GFCI Breaker
Going To Neutral
Bar In Box
Ground Bar
Attached To Box
(Green) Input & Out
From House To Box (Red)
Input
From House To Box (Black)
Input
Load Neutral Bar
From House To Box Neutral
(White) Input
Ground (Green)
Input
BREAKER BOX
G.F.C.I. Breaker
NOTE: The White Neutral Wire from the GFCI
MUST be connected to an incoming Line Neutral.
The internal mechanism of the GFCI requires
this Neutral connection. The GFCI
WILL NOT
WORK WITHOUT IT.
WARNING - ALWAYS USE A CERTIFIED ELECTRICIAN WHEN HOOKING UP YOUR NEW SPA.
3
Figure 1
(G.F.C.I. NOT INCLUDED)