Copyright 2017 Planika Sp. z o.o.
www.planikafires.com
i1086#04
18.10.2017
2
•
Do not install the device in areas with a capacity of less than 58 m
3
/ 2.049 ft
3
(22 m
2
/ 240 ft
2
with
a height of 2.6 m / 8.53 ft).
•
While installing the device according to the instruction manual local and national guidelines are
to be observed.
•
Place the device on a levelled surface. The cavity for the fireplace has to be designed with the
use of a spirit level.
•
It is not permitted to use the fireplace that is not placed in a housing. The cavity has to be
designed according to the guidelines and dimensions in the instruction manual. If the cavity has
different dimensions it has to be adjusted in such a way that it complies with the guidelines
stated in the installation manual.
•
Do not obstruct the ventilation slots and/or ventilators.
•
Do not place any decorative elements on the device.
•
Do not install the device in areas of large drafts of air, near fans, vents, etc.
•
Do not place in areas where there might be a potentially explosive atmosphere of paint vapours,
industrial dusts, etc.
•
No flammable items should be placed in direct contact and within a radius of 1 m / 3.28 ft around
the device. Do not place near curtains, net curtains, etc.
•
Do not expose the device to weather conditions. The product is for internal use only.
•
Do not expose the device to meteorological conditions. The device is for indoor use only.
•
Do not place the device in close proximity to sources of humidity.
•
It is obligatory to have a carbon-dioxide (CO
2
) or dry chemical extinguisher placed nearby the
device.
•
Installation of the device must provide an easy removal of the device for service.
•
The room in which the device will be installed must have efficient ventilation to ensure air
exchange in the room at least once per hour.
•
Do not start the device before a complete and proper installation.
•
Do not fill the fuel container before placing the product into its final position.
•
In case of mounting more than one unit in the room, the minimal cubature is the sum of
cubatures required for each unit.
•
The recess, into which the fireplace will be mounted, has to have a load capacity of 22,5 kg
(49,6lb).
•
Device must be kept out of reach of children, animals and unauthorized persons.
•
Do not install the device on a mobile object (eg. caravan, yacht )
.
!