PKP DS04.1 Instruction Manual Download Page 6

Connecting devices equipped with Reed switches

Reed switches are basically designed for small contact ratings. To connect a load with
higher power consumption it is indispensable to use a contact protection relay (e.g. our
series MSR01)
If you connect directly a load to a Reed contact the following recommendations should be
considered.
None of the contact rating values printed on the switching unit must not to be exceeded,
even momentarily. This is valid for each of the given values individually: voltage, current,
power. The Reed contact integrated in the switching unit is very sensible to electrical over-
load

Danger of overload is given by the following applications:

inductive load

capacitive load

lamp load

Inductive Load

Inductive loads consist e.g. of relay, contactors, solenoid valves, motors, electric engines,
etc.

WARNING: Voltage spikes at shut down (up to 10 times of nominal voltage)

Protective measures: (examples)

(Flyback diode, e.g. type 1N4007)

Capacitive Load

Capacitive loads consist e.g. of long connection cables or  capacitive consumers.

WARNING: High current spikes at switching on (this will exceed the nominal current)

Protective measures: (examples)

Limitation of current by a resistor

DS04 Instruction manual  03/2020

page  6

Summary of Contents for DS04.1

Page 1: ...anual DS04 All Metal Variable Area Flowmeter and Switch High Pressure Version PKP Prozessmesstechnik GmbH Borsigstra e 24 D 65205 Wiesbaden Nordenstadt Tel 49 0 6122 7055 0 Fax 49 0 6122 7055 50 Email...

Page 2: ...improper use non observance of this operating manual use of insufficiently qualified personnel and unau thorized modification of the device Proper Usage The variable area flowmeters of the DS04 series...

Page 3: ...mount the devices correctly Qualified personnel are persons who are familiar with assembling installation placing in service and operating these devices and who are suit ably trained and qualified Inw...

Page 4: ...damage to the flow monitor or the system a process connection suitable for the device must be provided by the customer check connection size and screw in depth use suitable sealants liquid sealants da...

Page 5: ...e case of liquid media take appropriate steps to ensure that the device is ven ted to ensure measuring accuracy the device must always be completely filled with medium vent the pipeline If there are a...

Page 6: ...ower The Reed contact integrated in the switching unit is very sensible to electrical over load Danger of overload is given by the following applications inductive load capacitive load lamp load Induc...

Page 7: ...directly connected to the input terminals of a PLC without problems RC Circuits as protective measures Boucherot cell Snubber In practice the following values of resistor capacitor cells give good re...

Page 8: ...re that the device is grounded via the pipeline This prevents dangerous potential differences from occurring Switching capacity of contacts Switching capacity Type Size Contact function Angle plug IP6...

Page 9: ...or acc to EN 175301 803 Normally Open NOC Change Over COC Switch position under no flow condition Switch position under no flow condition The ground pin is not used The ground pin is not used DS04 Ins...

Page 10: ...der no flow condition Switch position under no flow condition Switching contact with cable The individual cores of the cable are numbered according to the following connection dia gram Normally Open N...

Page 11: ...2 Slide the switch contact to the flow value to be monitored Make sure that the arrow on the switch contact label is in exact alignment with the desired flow value on the body scale 3 Re tighten the...

Page 12: ...Switch contact is permanently switched Flow is too high or the switch contact is set too low Reduce the flow Adjust the switch contact to a higher flow rate Use the device at another measuring range...

Page 13: ...s and circumstances Maintenance work Visual inspection for dirt soiling Visual inspection for free movement of float Visual inspection for leaks from the device Check function of switch contact For de...

Page 14: ...s following the float position indicates the flow rate on a scale A Reed contact is mounted outside the meter in a sealed housing When the float reaches the position of the Reed contact the switch wil...

Page 15: ...1 4 1N 1 4 NPT 1A G 3 8 1AN 3 8 NPT 2 G 1 2 2N 1 2 NPT 3 G 3 4 3N 3 4 NPT 4 G 1 4N 1 NPT Material 1 brass nickel plated 2 stainless steel 1 4571 Scale 1 for water 2 for air at 1 bar abs 20 C Measurin...

Page 16: ...800 900 05 27 32 30 35 47 47 71 71 1 2 3 4 19 17 146 174 800 850 960 1010 06 07 08 34 40 50 40 40 40 57 57 67 76 76 81 3 4 1 1 18 19 20 152 156 200 1350 1400 1050 1100 2750 2800 PKP Prozessmesstechnik...

Page 17: ...r operating densities deviating from the specified specifications increase the specified measuring error Special scales for different media and operating conditions are available on request The specif...

Reviews: