Additional programming of more parameters for display with
pulse and analogue output (Type B and D2)
Analogue minimum flow rate
Indicated by a “L” on the left hand side of the display, this screen allows the setting of the
flow rate that corresponds to the 4 mA output:
NOTE:
The minimum flow rate value must be less that the maximum flow rate value.
•
Minimum 0.0 LPM/GPM
•
Maximum 100.0 LPM/GPM
•
Default 0.0 LPM/GPM
NOTE:
Error checking will not allow the user to advance to the next screen.
To advance to the next programming screen, hold the TOTAL button for one second.
Analogue minimum flow rate screen
Analogue maximum flow rate
Indicated by a “H” on the left hand side of the display, this screen allows the setting of the
flow rate that corresponds to the 20mA output:
NOTE:
The maximum flow rate value must be greater than the minimum flow rate value.
•
Minimum 0.0 LPM/GPM
•
Maximum 100.0 LPM/GPM
•
Default 30 LPM / 8 GPM
To advance to the next programming screen, hold the TOTAL button.
NOTE:
Error checking will not allow the user to advance to the next screen.
Analogue maximum flow rate screen
DOZ03 / DOZ05 / DOZ07 Instruction manual 02/2021