![Pixsys ATR 421 User Manual Download Page 31](http://html1.mh-extra.com/html/pixsys/atr-421/atr-421_user-manual_1560818031.webp)
ATR 421 - User manual
31
Modbus
address
Description
Read
Write
Reset
value
1002
Setpoint (with gradient)
RO
0
1003
Setpoint with process decimal point selection
RO
0
1004
Digital input status
0
= input OFF
1
= input ON
RO
0
1005
Relay status (0=off , 1=on)
Bit 0 = relay
Q4
Bit 3 = relay
Q2
Bit 1 = relay
Q3
Bit 4 = relay
Q1 n.c.
Bit 2 = relay
Q1
n.o. Bit 5 =
SSR
RO
0
1006
Heating output percentage (0-10000)
RO
0
1007
Cooling output percentage (0-10000)
RO
0
1008
Heating output percentage (0-1000)
RO
0
1009
Cooling output percentage (0-1000)
RO
0
1010
Heating output percentage (0-100)
0
1011
Cooling output percentage (0-100)
RO
0
1012
Alarms status (0=none, 1=active)
Bit0 = Alarm 1
Bit2 = Alarm 3
Bit1 = Alarm 2
Bit3 = Alarm 4
RO
0
1013
Error fl ags
Bit0 = Eeprom writing error
Bit1 = Eeprom reading error
Bit2 = Cold juntion error
Bit3 = Error AI1 (sensor 1)
Bit4 = Error AI2 (sensor 2 - potentiometer)
Bit5 = Generic error
Bit6 = Hardware error
Bit7 = Missing calibration error
Bit8 = Eeprom cycle reading error
Bit9 = Not calibrate feedback potentiometer error
RO
0
1014
Cold juntion temperature (degrees with tenth)
RO
-
1200
Cycle selection for remote start
1
= cycle1
…
15
= cycle15
16
= controller
17
= output manual control
R/W
1
Summary of Contents for ATR 421
Page 1: ...ATR 421 Controller Regolatore User manual Manuale d uso...
Page 2: ......
Page 106: ...106 ATR 421 Manuale uso...
Page 107: ......