Spin Fryer I12 Cooking Computer
Pitco P/N 60149505
Page 13 of 28
L22-355 Rev 1
4
To Enter Programming Level 3 (for the Technician)
With no cook timers running, displays will show one of the following displays:
;
, or
.
Press the
key. The left display will show
. The right display
will be blank.
Enter password
6
8
6
5
Level 3 Password
using the product keys as a numeric keypad for
entry.
Display will show
. Product key indicators will
illuminate to prompt operator to select a key. This section details
parameters that may be changed in Level 3 programming.
4.1
Offset the Temperature Display:
This adjustment allows the displayed temperature value to be offset to reflect the true
center vat temperature while reading the probe tip temperature. Default value is +2.
With zero value set, displayed values are the probe temperature.
With display showing
press product key
1
.
Display shows [OFF nn F] [DEGREES], where “nn” is the value of the adjustment.
Negative values are preceded with a minus sign. To change this value, use the product keys
for numeric entry of a new value.
Press the
key. Display will show [POSITIVE] [DEGREES]. Use the product key to scroll
choices (Positive or Negative value).
After selection, press the
key. Display shows
.
Note: Computer Display Temp – Center Vat Temp = Offset (+/-). Example: Computer Display shows
350F while Center Vat Temp measures 352F. 350F – 352F = - 2 °F. A negative offset value.
Proper
equipment and expertise is required to correctly adjust this value.
Even
s
mall changes may negatively
affect cooking performance.
4.2
Melt Cycle ON Time
With display showing
press product key
2
.
Display shows [MLTON :nn] [MELT ON], where “nn” is the value, in seconds, of time
for a melt cycle heat pulse.
To change this value, use the product keys for numeric entry of a new value.
Press the
key. Display returns to
.
1
2