Panel Lock setting
Set panel lock
In the Operation mode, press ▲ button for 4 seconds or more. "PL" flashes 3 times and panel
lock is set. Start displaying pressure again after setting.
In the Operation mode, press ▼ button for more than 4 seconds. "PA" flashes 3 times and
the panel lock is cancelled. Start displaying pressure again after cancellation.
"PL" flashes 3 times when there is some operation during panel lock setting,
start displaying pressure display again. Operation is not accepted.
Operations during panel lock setting
Cancel panel lock
The procedure in which indication pressure values are taken as operating pressure setting of SW1, SW2 <Auto-reference mode>
Enter the Auto-reference mode from the
Selection mode according to "Panel
Operation Procedure, ① Mode Selection".
When the display pressure flashes with applying a pressure wanting to be set, press the
▲ button to set the SW1 switch pressure and press the ▼ button to set the SW2 switch
pressure. When you press the button, the flashing speed of the screen will be faster.
The auto reference mode is a function in which the indication pressure
can be taken automatically as the operating pressure set value of SW1,
SW2 by button operation.
After setting Switch pressure of SW1
▼and▲ SW2, press and a buttons
simultaneously for more than 1 second to
save the setting. Return to Operation
mode and start displaying pressure.
Cautions
When the
▲
or
▼
button is pressed, if the input pressure to the sensor exceeds the set range of Switch pressure value of SW1 and SW2 in
the "Switch Setting mode , or window-comparator mode is selected by Switch Output Action in the "Initial Setting mode and "P1 SP2
≦
2His not
satisfied, error "E1" is displayed. By pressing the
▲
button while "E1" error displaying, the process will return to the save stand-by state of Switch
pressure setting of SW1 or SW2.
13.
Panel Operation Procedure
Error No.
Flashing indication
Error details
Setting condition
Check timing
How to clear the Error Pronty
Flash ROM error
Checksum abnormality
Sensor activation
Zero point correction
in Zero Adjusting mode
Please consult the
nearest Pisco office
during pressure
detection
Re-activate the
sensor by reboot
Make detecting
pressure
≦
110%
F.S
Pressing ▲ button
Pressing ▲ button
Operation mode
When saving the swich pressure
value of SW1 and SW2 in
Auto-reference mode
Abnormal setting value for
Auto-reference mode
The input pressure to the sensor is out of the
set switch pressure range, or "P1 P2
≦
2H" is
not satisfied in the Window-comparator mode
Detecting pressure s-5% below the minimum
display pressure range, or +5%
≦
above the
maximum display pressure range
"P1
≦
P2 - 2H" is not satisfied in the
window- comparator made
Derecting pressure > 100%F.S
Pressuring while setting
Zero Adjusting mode
Detected pressure
exceeds 110% F.S
Parameter abnormality
occurs during pressure
detection