
Symptom
:
System
does
not
automatically
restart
after
a
power
failure.
Reason
:
Auto
Restart
Function
has
been
turned
OFF.
Solution
:
Turn
OFF
the
breaker,
Press
and
hold
the
emergency
restart
button
and
turn
the
breaker
ON
while
still
holding
the
button
pressed
for
10
more
seconds.
5
beeps
indicate
activation
of
the
Auto
Restart
function.
Repeat
the
procedure
for
tuning
OFF
the
auto
restart
function
in
not
desired
(Indicated
by
3
beeps).
Symptom
:
Indoor
unit
blows
smelly
air.
Reason
:
Dirty
filters
and/or
evaporator
coil.
Solution
:
Clean
the
filters.
If
the
coil
is
dirty
have
the
evaporator
professionally
cleaned.
Run
the
unit
for
several
hours
in
FAN
ONLY
mode
to
dry
it
before
preparing
to
leave
the
system
OFF
for
long
periods
of
time.
Symptom
:
Uncomfortably
wide
temperature
swings
in
the
room.
Reason
:
Indoor
unit
installed
too
high,
filters
dirty,
Room
temperature
sensor
deficiency.
Solution
:
Higher
locations
in
the
room
will
have
warmer
temperatures
and
the
system
will
measure
the
temperature
at
the
height
the
indoor
unit
is
installed.
User
can
compensate
for
this
by
setting
the
temperature
settings
slightly
lower
or
higher
than
actually
desired.
Clean
the
filters
weekly
for
best
performance.
Check
the
return
air
sensor
and
replace
if
needed.
Symptom
:
System
does
not
respond
to
commands
from
the
remote
controller.
Reason
:
Remote
is
located
far
away,
weak
remote
batteries,
disconnected
display
board/
Solution
:
Place
the
remote
nearby
and
retry.
Replace
the
batteries.
Check
the
connection
cable
between
the
display
board
and
the
main
controller
board.
Electrical
/
Wiring
Diagnostics:
1.
110
‐
120
VAC
Models:
a.
Check
the
voltage
between
the
L
and
N
terminals
on
the
indoor
unit.
It
should
be
always
110~120V.
b.
Check
the
voltage
between
the
L
and
N
terminals
on
the
outdoor
unit.
It
should
be
always
110~120V.
c.
Check
the
voltage
between
two
L
terminals
(left
and
right)
on
the
outdoor
unit.
It
should
always
0
V.
d.
For
the
compressor
to
run,
the
voltage
between
the
1
and
N
terminals
at
BOTH
the
outdoor
and
indoor
units'
terminal
blocks
must
be
measured
as
110~120
VAC.
e.
For
the
outdoor
fan
motor
to
run,
the
voltage
between
the
2
and
N
terminals
at
BOTH
the
outdoor
and
indoor
units'
terminal
blocks
must
be
measured
as
110~120
VAC.
f.
For
the
heat
mode
to
be
activated,
the
voltage
between
the
3
and
N
terminals
at
BOTH
the
outdoor
and
indoor
units'
terminal
blocks
must
be
measured
as
110~120
VAC.
2.
208
‐
230
VAC
Models:
a.
Check
the
voltage
between
the
L1
and
L2
terminals
on
the
indoor
unit.
It
should
be
always
208~230V.
b.
Check
the
voltage
between
the
L1
and
L2
terminals
on
the
outdoor
unit.
It
should
be
always
208~230V.
c.
Check
the
voltage
between
two
L1
terminals
(left
and
right)
on
the
outdoor
unit.
It
should
always
0
V.
d.
For
the
compressor
to
run,
the
voltage
between
the
1
and
L2
terminals
at
BOTH
the
outdoor
and
indoor
units'
terminal
blocks
must
be
measured
as
208~230
VAC.
e.
For
the
outdoor
fan
motor
to
run,
the
voltage
between
the
2
and
L2
terminals
at
BOTH
the
outdoor
and
indoor
units'
terminal
blocks
must
be
measured
as
208~230
VAC.
(#2
is
not
accessible
for
024
Indoor).
f.
For
the
heat
mode
to
be
activated,
the
voltage
between
the
3
and
L2
terminals
at
BOTH
the
outdoor
and
indoor
units'
terminal
blocks
must
be
measured
as
208~230
VAC.
(#3
is
not
accessible
for
024
Indoor).
Piping
Surface
Temperature
Diagnostics:
a.
In
Cooling
mode,
the
smaller
diameter
pipe
must
feel
Very
Cold
and
the
larger
diameter
pipe
must
feel
Cold.
b.
In
Heating
mode,
the
smaller
diameter
pipe
must
feel
Hot
and
the
larger
diameter
pipe
must
feel
Very
Hot.