Pioneer WYD009AL3JAR-L Service Manual Download Page 15

 

Symptom

 

:

 

In

 

HEAT

 

Mode,

 

indoor

 

unit

 

is

 

blowing

 

cold

 

air

 

instead

 

of

 

heating.

 

Reason

  

:

 

Missing

 

wire

 

connection,

 

defective

 

reversing

 

valve

 

actuator.

 

Solution

 

:

 

Otherwise,

 

assure

 

that

 

the

 

YELLOW

 

wire

 

is

 

attached

 

to

 

terminal

 

#3

 

on

 

the

 

outdoor

 

unit.

 

Also

 

check

 

that

 

the

 

same

 

yellow

 

wire

 

is

 

either

 

connected

 

to

 

the

 

#3

 

terminal

 

on

 

the

 

indoor

 

unit

 

(009,

 

012,

 

018

 

models)

 

or

 

the

 

white

 

plug

 

at

 

the

 

end

 

of

 

the

 

cable

 

at

 

the

 

indoor

 

side

 

is

 

plugged

 

with

 

the

 

matching

 

white

 

plug

 

on

 

the

 

indoor

 

unit

 

properly

 

(for

 

024

 

models

 

only).

 

While

 

in

 

Heat

 

Mode:

 

Check

 

for

 

voltage

 

between

 

#3

 

and

 

N

 

terminals

 

on

 

115V

 

models

 

and

 

assure

 

it

 

reads

 

115V

 

or

 

check

 

between

 

#3

 

and

 

L2

 

terminals

 

on

 

230V

 

models

 

and

 

assure

 

it

 

reads

 

230V

 

(at

 

the

 

outdoor

 

unit's

 

terminal

 

block).

 

 

Symptom

 

:

 

Both

 

indoor

 

and

 

outdoor

 

units

 

run

 

but

 

there

 

is

 

no

 

heating

 

or

 

cooling.

 

Reason

  

:

 

Valves

 

were

 

not

 

fully

 

opened,

 

like

 

set

 

is

 

kinked,

 

refrigerant

 

was

 

lost.

 

Solution

 

:

 

Assure

 

that

 

the

 

system

 

was

 

properly

 

vacuumed

 

before

 

releasing

 

the

 

refrigerant.

 

Assure

 

both

 

valves

 

on

 

the

 

outdoor

 

unit

 

were

 

fully

 

opened.

 

Assure

 

there

 

are

 

no

 

refrigerant

 

leak

 

at

 

any

 

of

 

the

 

4

 

flare

 

connections

 

attached

 

during

 

installation.

 

Check

 

for

 

pressure

 

reading

 

in

 

cool

 

mode

 

to

 

be

 

approx

 

120

 

PSI

 

and

 

both

 

copper

 

pipes

 

to

 

be

 

very

 

cold

 

and

 

sweating.

 

Check

 

for

 

pressure

 

reading

 

in

 

heat

 

mode

 

to

 

be

 

approx

 

400

 

PSI

 

and

 

both

 

copper

 

pipes

 

to

 

be

 

very

 

hot.

 

 

Symptom

 

:

 

In

 

heat

 

mode

 

outdoor

 

unit

 

runs

 

but

 

indoor

 

unit

 

fan

 

does

 

not

 

start

 

blowing.

 

Reason

  

:

 

System

 

is

 

in

 

warm

 

Start

 

Mode.

 

If

 

extended

 

this

 

can

 

mean

 

refrigerant

 

loss.

 

Solution

 

:

 

When

 

the

 

compressor

 

first

 

starts

 

in

 

heat

 

mode,

 

indoor

 

fan

 

is

 

delayed

 

until

 

the

 

indoor

 

coil

 

surface

 

gets

 

hot

 

enough

 

to

 

produce

 

warm

 

air

 

discharge.

 

The

 

fan

 

starts

 

blowing

 

once

 

the

 

indoor

 

coil

 

is

 

warmed.

 

This

 

takes

 

maximum

 

1

 

minute.

 

If

 

this

 

is

 

extended

 

further,

 

than

 

check

 

for

 

operating

 

pressures

 

and

 

assure

 

the

 

system

 

has

 

no

 

refrigerant

 

leaks.

 

 

Symptom

 

:

 

System

 

does

 

not

 

start

 

cooling

 

or

 

heating

 

as

 

soon

 

as

 

it

 

is

 

started.

 

Reason

  

:

 

System

 

is

 

in

 

protection

 

time

 

delay

 

mode.

 

Solution

 

:

 

When

 

the

 

system

 

is

 

started,

 

the

 

compressor

 

does

 

not

 

start

 

immediately.

 

There

 

is

 

a

 

3

 

minute

 

time

 

delay

 

for

 

protection.

 

 

Symptom

 

:

 

Indoor

 

unit

 

seems

 

totally

 

dead.

 

No

 

lights.

 

Reason

  

:

 

Power

 

connection

 

from

 

the

 

outdoor

 

unit

 

is

 

not

 

made

 

properly

 

or

 

fuse

 

was

 

blown.

 

Solution

 

:

 

Check

 

for

 

the

 

voltage

 

between

 

L

 

and

 

N

 

terminals

 

on

 

the

 

indoor

 

units

 

terminal

 

block

 

(for

 

115V

 

systems)

 

to

 

read

 

115

 

VAC.

 

Check

 

for

 

the

 

voltage

 

between

 

L1

 

and

 

L2

 

terminals

 

on

 

the

 

indoor

 

units

 

terminal

 

block

 

(for

 

230V

 

systems)

 

to

 

read

 

230

 

VAC.

 

Check

 

the

 

other

 

end

 

of

 

the

 

same

 

wires

 

on

 

the

 

outdoor

 

unit

 

for

 

the

 

same

 

voltage.

 

Assure

 

the

 

breaker

 

is

 

not

 

tripped.

 

If

 

the

 

voltage

 

is

 

present

 

on

 

the

 

indoor

 

unit,

 

fuse

 

may

 

be

 

blown

 

on

 

the

 

controller

 

card

 

of

 

the

 

indoor

 

unit.

 

Replace

 

with

 

a

 

5A

 

fuse.

 

Or

 

replace

 

the

 

control

 

card.

 

 

Symptom

 

:

 

Indoor

 

unit

 

fan

 

runs

 

continuously

 

in

 

cooling

 

mode.

 

Reason

  

:

 

This

 

is

 

a

 

normal

 

and

 

required

 

condition

 

programmed

 

by

 

the

 

internal

 

software.

 

Solution

 

:

 

Indoor

 

fan

 

must

 

run

 

continually

 

in

 

cooling

 

mode

 

to

 

be

 

able

 

to

 

sample

 

the

 

air

 

temperature

 

and

 

call

 

for

 

the

 

compressor

 

to

 

cycle

 

on

 

when

 

needed.

 

This

 

is

 

normal.

 

Indoor

 

fan

 

motor

 

operates

 

on

 

only

 

a

 

few

 

pennies

 

a

 

day,

 

so

 

it

 

will

 

not

 

waste

 

any

 

significant

 

amount

 

of

 

energy,

 

plus

 

it

 

will

 

provide

 

a

 

positive

 

air

 

circulation

 

for

 

better

 

comfort.

 

 

Symptom

 

:

 

Indoor

 

unit

 

fan

 

comes

 

on

 

and

 

off

 

briefly

 

in

 

heat

 

mode.

 

Reason

  

:

 

This

 

is

 

a

 

normal

 

and

 

required

 

condition

 

programmed

 

by

 

the

 

internal

 

software.

 

Solution

 

:

 

Indoor

 

fan

 

must

 

runs

 

once

 

in

 

a

 

while

 

to

 

sample

 

the

 

air

 

temperature

 

and

 

call

 

for

 

the

 

compressor

 

to

 

cycle

 

on

 

when

 

needed.

 

This

 

is

 

normal.

 

Unlike

 

the

 

cooling

 

mode,

 

indoor

 

fan

 

does

 

not

 

run

 

continually

 

in

 

cooling

 

mode

 

to

 

prevent

 

cols

 

air

 

draft.

 

The

 

temperature

 

swings

 

in

 

the

 

space

 

between

 

the

 

on

 

and

 

off

 

modes

 

will

 

be

 

slightly

 

higher

 

than

 

the

 

cooling

 

mode.

 

 

Summary of Contents for WYD009AL3JAR-L

Page 1: ... No TE1307 Models WYD009AL3JAR L WYD012AL3JAR L WYD018GL3JAR L WYD024GL3JAR L 1 IMPORTANT NOTICE 2 OPERATION DETAILS 3 ELECTRICAL SCHEMATIC DIAGRAM 4 EXPLOSION VIEW 5 PARTS LIST WALL MOUNTED SPLIT TYPEAIR CONDITIONERS CONTENTS 1 2 11 13 16 ...

Page 2: ...not be responsible for the interpretation of this information nor can it assume any liability in connection with its use The information specifications and parameter are subject to change due to technical modification or improvement without any prior notice The accurate specifications are presented on the nameplate label How to order spare parts To have your order filled promptly and correctly ple...

Page 3: ...ote controller 6 2 5 3 7 1 Air Conditioner Service Manual Operation Details Remote Control The remote controller is not preset as Cooling Only Air Conditioner or Heat Pump by manufacturer Each time after the remote controller replace batteries or is energized the arrowhead will flash on the front of Heat or Cool on LCD of the remote controller User can preset the remote controller type depending o...

Page 4: ...ressor Outdoor fan OFF when the indoor pipe temperature is ı Outdoor fan ON when the indoor pipe temperature is İ118 4 Compressor OFF when the indoor pipe temperature is ı Compressor ON when the indoor pipe temperature is İ118 4 2 I Feel Mode Operation 1 When the I Feel mode is selected the operation mode and initial set temperature are determined by the initial room temperature at start up of the...

Page 5: ...setting temperature the system will set the temperature at automatically with the AUTO FAN speed 2 When selecting the HEATING mode operation the system will operate according to the setting by the remote controller and the operation is as following Set Temp ˇ1 8 Set Temp ˉ1 8 Room Temp Time More than 2 min More than 2 min More than 2 min More than 2 min More than 2 min Compressor ON OFF ON OFF ON ...

Page 6: ... the IPT is less than for 2 minutes When the defrosting operation time on this condition exceeds 8 minutes it will terminate C After the compressor operates continuously for 20 minutes and the IPT is less than 73 4 or from the last time of defrosting operation is 50 minutes or more interval When the defrosting operation time on this condition exceeds 10 minutes it will terminate z When the JC isn ...

Page 7: ...e the set temperature will be raised by 1 1 hour later and by 2 hour later z When selecting HEATING operation with SLEEP mode the set temperature will be dropped by 1 1 hour later and 2 hour later z After the System operates in SLEEP mode for 8 hours it will stop automatically 9 Fan motor control 1 Rotational frequency feedback control The indoor fan motor is equipped with a rotational frequency s...

Page 8: ...on and then set to the desired angle The positioning is decided as follows z When the ON OFF button is pressed z When the vane control is change from AUTO to MANUAL z When the SWING is finished z When the test run starts z When the power supply turns ON 3 The auto vane changes as follows by pressing the VANE CONTROL button 4 VANE AUTO mode In vane auto mode the microprocessor automatically determi...

Page 9: ...pressed or a button on the remote controller is pressed and normal operation will start NOTE Do not press the EMERGEMCY Operation switch during normal operation 14 AUTO RESTART Function Option 1 When the indoor unit is controlled with the remote controller the operation mode set temperature and the fan speed are memorized by the indoor electric control PCB The AUTO RESTART function sets to work th...

Page 10: ...l of remoter controller except the signal of shut off When the system checks the voltage is 220V and the delay control is finished it operates at normal again z When the indoor fan motor is failure the compressor is stopped the outdoor fan and indoor fan is stopped and display the failure The system doesn t receive the signal of remoter controller except the signal of shut it off d Display Of The ...

Page 11: ...Wiring diagram Model 5 5 Indoor unit Outdoor unit ...

Page 12: ...Wiring diagram Model 5 Indoor unit Outdoor unit ...

Page 13: ...Wiring diagram Model 5 Indoor unit Outdoor unit ...

Page 14: ... motor is properly mounted If the blower is spinning freely and E6 code is still displayed change the fan motor If this does not resolve the problem change the indoor unit s controller card Symptom HEAT Mode is missing on the remote control screen Remote skips the heat mode Reason Remote controller was erroneously setup as cooling only Solution Reset the remote controller Remove and reinsert the b...

Page 15: ...heck for operating pressures and assure the system has no refrigerant leaks Symptom System does not start cooling or heating as soon as it is started Reason System is in protection time delay mode Solution When the system is started the compressor does not start immediately There is a 3 minute time delay for protection Symptom Indoor unit seems totally dead No lights Reason Power connection from t...

Page 16: ...he system will stop defrosting and switch to heating mode again Additionally system cannot operate in heating mode at outdoor temperatures below 15F which will be in efficient and causes more frequent freezing than normal Otherwise check for low refrigerant charge and measure the pressures and obtain proper levels Clean the coil if needed Symptom Circuit breaker tripping Reason Damaged breaker low...

Page 17: ...door unit It should be always 110 120V b Check the voltage between the L and N terminals on the outdoor unit It should be always 110 120V c Check the voltage between two L terminals left and right on the outdoor unit It should always 0 V d For the compressor to run the voltage between the 1 and N terminals at BOTH the outdoor and indoor units terminal blocks must be measured as 110 120 VAC e For t...

Reviews: