37
2. INDOOR COMBUSTION AIR INSTALLATION IN CONFINED OR UNCONFINED SPACE
This heater requires fresh, uncontaminated air for safe operation and must be installed in a mechanical
room where there is adequate combustion and ventilating air.
NOTE: To prevent combustion air
contamination, see Table 1.
Combustion air from the indoor space can be used if
the space has adequate area or when air is
provided through a duct or louver to supply sufficient
combustion air based on the appliance input.
Never
obstruct the supply of combustion air to the
appliance.
If the appliance is installed in areas
where indoor air is contaminated (see Figure 15) it
is imperative that the appliance be installed as direct
vent so that all combustion air is taken directly from
the outdoors into the appliance intake connection.
Unconfined space
is space with volume not less
than 50 cubic feet per 1,000 Btu/hour (4.8 cubic
meters per kW) of the total input rating of all fuel-
burning appliances installed in that space. Rooms
connected directly to this space, through openings
not furnished with doors, are considered part of the
space.
Confined space
is space with volume less than 50
cubic feet per 1,000 Btu/hour (4.8 cubic meters per
kW) of the total input rating of all fuel-burning
appliances installed in that space. Rooms
connected directly to this space, through openings
not furnished with doors, are considered part of the
space.
When drawing combustion air from inside a
conventionally constructed building to a confined
space, such space should be provided with two permanent openings: one located 6” (15 cm) below the
space ceiling, the other 6” (15cm) above the space floor. Each opening should have a free area of one
square inch per 1,000 Btu/hr (22cm
2
/kW) of the total input of all appliances in the space, but not less than
100 square inches (645cm
2
).
If the confined space is within a building of tight construction, air for combustion must be obtained from
the outdoors as outlined in the Venting section of this manual.
Figure 15 – LP-179-AA