Function description
Operating Manual PSSu E S INC 24V se(-T)
1001380-EN-04
21
Key to timing diagram:
Section Function
Procedure for PSSu in sys-
tem environment A
Procedure for PSSu in sys-
tem environment B
a
Activate monitor-
ing function
In the user program, set Bit 3
of the function call. Output
O0 ("0" or "1") is set based
on Bit 4 of the function call
In the user program, set Out-
putData.LimitValueActive
b
Limit value
reached
Output O0 ("0" or "1") is set
based on Bit 4 of the function
call
Output O0 ("0" or "1") is set
based on OutputData.Inver-
tOutput
c
Output polarity
changed
In the user program, set Bit 4
of the function call. Output
O0 switches polarity
In the user program, set Out-
putData.InvertOutput. Output
O0 switches polarity
d
Limit value
reached
Output O0 ("0" or "1") is set
based on Bit 4 of the function
call
Output O0 ("0" or "1") is set
based on OutputData.Inver-
tOutput
4.3
Configuration
4.3.1
Operating modes and parameters
The module has the following configuration options:
Configuration
Default
value
Meaning
Operating mode
X
Incremental encoder operating mode
Counter operating mode
Signal for gate input
X
Input G disables at a 1 signal
Input G disables at a 0 signal
Period length measure-
ment or latch function
X
Latch function
Period length measurement
Multiple evaluation
X
Quadruple evaluation
Double evaluation
Single evaluation
Status input
X
The status at input S is transmitted via a bit.
The status is transmitted via two redundant bits.
The status is transmitted via two diverse bits.
(1)
(1)
Transmitting the status via two bits enables simple fault detection: Two redundant bits
must always be the same, two diverse bits must always be different, otherwise the trans-
mission is faulty.