Wiring
Operating Manual PSSu E F DI OZ 2(-T)(-R)
21328-EN-10
28
Output circuit
Without C-rail
Dual-channel operation
Redundant actuator
11
12
13
14
21
22
23
24
O0+
I0
O0-
n. c.
n.c.
n.c.
T0
T0
K1
11
12
13
14
21
22
23
24
O0+
I0
O0-
n. c.
n.c.
n.c.
T0
T0
K2
L1
K1
K2
M
K1
K2
RFK
6.4
Function test during commissioning
An error must be simulated for each safety-related output during commissioning: The anti-
cipated error reaction must occur when an output has a short circuit to a supply voltage.
INFORMATION
The short circuit test must be performed on the load and not on the output
terminal.