Wiring
Operating Manual PSSu E F DI OZ 2(-T)(-R)
21328-EN-10
24
6
Wiring
6.1
General wiring guidelines
Please note:
}
The actuators may be connected using unshielded cables.
}
The outputs do not need suppression for inductive loads.
}
Use copper wiring.
}
The terminal configuration as stated on the front plate applies for base modules with C-
rail. The terminal configuration as stated in the technical documentation applies for all
other base modules.
6.1.1
Mechanical connection of the base modules
Procedure:
}
Use a flat blade screwdriver (DIN 5264-A)!
DIN 5264-A
}
Strip the wire back 8 mm.
}
If necessary, label the connection level with a colour marker [3].
}
Base module with screw terminals:
–
Use a screwdriver to loosen the screw on the screw terminal [1]
–
Insert the stripped cable into the round fixing hole [2], as far as it will go.
–
Tighten up the screw on the screw terminal.
–
Check that the cable is firmly seated.
}
Base module with cage clamp terminals:
–
Insert the screwdriver [4] into the square hole [1].
–
Insert the stripped cable into the round fixing hole [2], as far as it will go [5].
–
Pull out the screwdriver [6].
–
Check that the cable is firmly seated.