Function description
Operating Manual PSSu E F DI OZ 2(-T)(-R)
21328-EN-10
14
Output
}
The head module sets the output status via the module bus.
}
The max. capacity at an output depends on the load (see characteristic). Connecting a
higher capacity may lead to an error.
}
Operation with electronic contactors has not been tested and may lead to errors.
Please contact our Customer Support team if you are using electronic contactors.
}
Open circuit detection
}
Cannot be used as a single-pole output
Test pulse output
}
Test pulses can be switched on or off.
}
Test pulses are switched on in the default setting.
}
When test pulses are switched off, the periphery supply is constantly available at the
output.
Output test (not configurable)
}
Outputs that are switched on are checked via regular off tests.
–
Test pulses for outputs that are switched on: see technical details
–
Outputs that are switched on are switched off for the duration of the test pulse.
–
The load must not switch off because of the test.
}
Outputs that are switched off are checked via regular on tests.
–
Test pulses for outputs that are switched off: see technical details
–
Outputs that are switched off are switched on for the duration of the test pulse.
–
The load must not switch on because of the test.
Testing for shorts
}
A test is regularly carried out to check for shorts between the outputs.
Open circuit detection
}
The module will detect an open circuit between outputs O0+ and O0-.
}
The result of open circuit detection is signalled to the head module via a virtual input.
The result is available within the user program:
–
No open circuit detected: Status bit set
–
Open circuit detected: Status bit not set
}
Loads over 3 kOhm may mistakenly be detected as an open circuit.