Installation
}
The unit can be installed in any position. However, safety switches and actuators must be
positioned opposite each other in parallel.
}
If possible, do not install the safety switch and actuator on to ferromagnetic material.
Changes to the operating distances are to be expected.
}
Safety switches and actuators should only be secured using M4 screws with a flat head
(e.g. M4 cheese-head or pan head screws). Use screws made of non-magnetic material
(e.g. brass).
CAUTION!
Potential loss of safety function due to changed device properties
The unit's properties may be affected if installed in an environment contain-
ing electrically or magnetically conductive material.
– Please check the operating distances and the assured release dis-
tance.
CAUTION!
Possible loss of the safety function by changing the release distance
S
ar
with non-flush installation
Installing the safety switch non-flush within electrically or magnetically con-
ductive material, the value for the assured release distance
S
ar
can change.
– Check the assured release distance
S
ar.
}
Safety switches and actuators must be positioned so that they are secured against a
change of position.
}
The safety switch and actuator should only be secured using screws and nuts made of
non-magnetic material (e.g. brass or stainless steel).
}
Avoid the risk of damages from foreseeable external influences by attaching the safety
switch and actuator. If necessary, safety switch and actuator have to be protected.
INFORMATION
Protect the actuator from unauthorised removal (e.g. via a screw lock or
concealed installation) and from contamination.
}
Prevent self-loosening of the fastening elements of safety switch and actuator.
}
The fastening of safety switch and actuator has to be sufficiently stable to ensure the
proper operation of the safety switch and the actuator.
}
The distance between two safety switches must be maintained (see
).