PSEN cs4.1p/M12
Operating Manual PSEN cs4.1p/M12
1003293-EN-08
| 29
Electrical data
541159
541160
No-load current
20 mA
20 mA
Inputs
541159
541160
Number
2
2
Voltage at inputs
24 V DC
24 V DC
Input current range
5 mA
5 mA
Max. overall cable resistance Rl-
max
Single-channel at UB DC
1000 Ohm
1000 Ohm
Semiconductor outputs
541159
541160
OSSD safety outputs
2
2
Signal outputs
1
1
Switching current per output
100 mA
100 mA
Breaking capacity per output
2,4 W
2,4 W
Potential isolation from system
voltage
No
No
Short circuit-proof
yes
yes
Residual current at outputs
20 µA
20 µA
Voltage drop at OSSDs
3,5 V
3,5 V
Lowest operating current
0 mA
0 mA
Utilisation category in accordance
with EN 60947-1
DC-12
DC-12
Times
541159
541160
Test pulse duration, safety outputs
450 µs
450 µs
Switch-on delay
after UB is applied
1 s
1 s
Inputs typ.
13 ms
13 ms
Inputs max.
20 ms
20 ms
Actuator typ.
60 ms
60 ms
Actuator max.
150 ms
150 ms
Delay-on de-energisation
Inputs typ.
15 ms
15 ms
Inputs max.
20 ms
20 ms
Actuator typ.
40 ms
40 ms
Actuator max.
260 ms
260 ms
Risk time in accordance with EN
60947-5-3
260 ms
260 ms
Supply interruption before de-ener-
gisation
10 ms
10 ms
Simultaneity, channel 1 and 2 max.
∞
∞
Environmental data
541159
541160
Ambient temperature
In accordance with the standard
EN 60068-2-14
EN 60068-2-14
Temperature range
-25 - 70 °C
-25 - 70 °C