Connection to control systems and evaluation devices
Operating Manual PSEN ml s 1.1/2.1/2.2
1004710-EN-05
| 33
Examples for cable lengths
}
Supply voltage at the safety control system ≥ 20.4 V
Number of safety
switches
L1
L2
L3
L4
L5
L6
Overall
length
1
50 m
50 m
2
30 m
20 m
50 m
3
20 m
10 m
10 m
40 m
4
20 m
5 m
5 m
5 m
35 m
5
10 m
5 m
5 m
5 m
5 m
30 m
6
5 m
5 m
5 m
5 m
5 m
5 m
30 m
}
Supply voltage at the safety control system ≥ 24 V
Number of safety
switches
L1
L2
L3
L4
L5
L6
Overall
length
1
120 m
120 m
2
60 m
60 m
120 m
3
50 m
50 m
20 m
120 m
4
50 m
30 m
20 m
20 m
120 m
5
50 m
20 m
20 m
20 m
10 m
120 m
6
20 m
20 m
20 m
20 m
20 m
20 m
120 m
}
Supply voltage at the safety control system ≥ 28.8 V
Number of safety
switches
L1
L2
L3
L4
L5
L6
Overall
length
1
180 m
180 m
2
130 m
50 m
180 m
3
80 m
50 m
50 m
180 m
4
50 m
50 m
50 m
30 m
180 m
5
50 m
50 m
30 m
30 m
20 m
180 m
6
50 m
50 m
20 m
20 m
20 m
20 m
180 m