Wiring
Operating Manual PSSu E PD1(-T)
21453-EN-04
17
6
Wiring
6.1
General wiring guidelines
Please note:
}
Safe electrical isolation must be ensured for the external supplies. Failure to do so
could result in electric shock.
}
The external power supplies must comply with the current applicable standard EN
60950-1, EN 61140, EN 50178 or EN 61558-1.
}
The maximum current load on the connection terminals is 4 A per supply.
}
Permitted infeed at the module's connection terminals:
– PE
– 0 V
– Shield
– - 30 VDC ... + 30 VDC
– - 48 VAC ... + 48 VAC
}
Use copper wiring.
}
The terminal configuration as stated on the front plate applies for base modules without
C-rail. The terminal configuration as stated in the technical documentation applies for all
other base modules.
6.1.1
Mechanical connection of the base modules
Procedure:
}
Use a flat blade screwdriver (DIN 5264-A)!
DIN 5264-A
}
Strip the wire back 8 mm.
}
If necessary, label the connection level with a colour marker [3].
}
Base module with screw terminals:
– Use a screwdriver to loosen the screw on the screw terminal [1]
– Insert the stripped cable into the round fixing hole [2], as far as it will go.
– Tighten up the screw on the screw terminal.
– Check that the cable is firmly seated.