background image

Introduction

Operating Manual PSSu E PD1(-T)
21453-EN-04

4

1

Introduction

1.1

Validity of documentation

This documentation is valid for the products PSSu E PD1 and PSSu E PD1-T. It is valid un-
til new documentation is published.
This operating manual explains the function and operation, describes the installation and
provides guidelines on how to connect the product.

1.1.1

Retaining the documentation

This documentation is intended for instruction and should be retained for future reference.

1.2

Definition of symbols

Information that is particularly important is identified as follows:

DANGER!

This warning must be heeded! It warns of a hazardous situation that poses
an immediate threat of serious injury and death and indicates preventive
measures that can be taken.

WARNING!

This warning must be heeded! It warns of a hazardous situation that could
lead to serious injury and death and indicates preventive measures that can
be taken.

CAUTION!

This refers to a hazard that can lead to a less serious or minor injury plus
material damage, and also provides information on preventive measures
that can be taken.

NOTICE

This describes a situation in which the product or devices could be dam-
aged and also provides information on preventive measures that can be
taken. It also highlights areas within the text that are of particular import-
ance.

Summary of Contents for 312196

Page 1: ...PSSu E PD1 T Operating Manual 21453 EN 04 Decentralised system PSSuniversal I O...

Page 2: ...KG Copies may be made for internal purposes Suggestions and comments for improving this documentation will be gratefully received Pilz PIT PMI PNOZ Primo PSEN PSS PVIS SafetyBUS p SafetyEYE SafetyNET...

Page 3: ...Functions 11 4 3 Configuration 11 4 3 1 Configuration 11 4 3 2 Addresses in the process image 11 Section 5 Installation 12 5 1 General installation guidelines 12 5 1 1 Dimensions 12 5 2 Installing the...

Page 4: ...ified as follows DANGER This warning must be heeded It warns of a hazardous situation that poses an immediate threat of serious injury and death and indicates preventive measures that can be taken WAR...

Page 5: ...Introduction Operating Manual PSSu E PD1 T 21453 EN 04 5 INFORMATION This gives advice on applications and provides information on special fea tures...

Page 6: ...connect the field wiring The electronic modules are inserted on to the base modules and determine the module s function Details of the base modules that can be used are available in the chapter entitl...

Page 7: ...2 41 P1 43 P3 44 P4 PSSu E PD1 312196 000000 001 10 1 3 4 9 8 5 6 7 2 A B Legend A Electronic module B Base module 1 Labelling strip with Name of electronic module Order number Serial number Hardware...

Page 8: ...ighten the screw terminal on base modules with screw termin als With mechanism to operate the cage clamp on base modules with cage clamp ter minals 9 Round connection holes connection levels 1 2 3 and...

Page 9: ...ctrical modification to the module Use of the module outside the areas described in this manual Any use of the module that is not in accordance with the technical details INFORMATION The module is sup...

Page 10: ...nder Safety And have a good knowledge of the generic and specialist standards applicable to the specific application 3 2 2 Warranty and liability All claims to warranty and liability will be rendered...

Page 11: ...is not available on the module s connection terminals External supplies The module provides connections for external supplies The module does not switch the external supplies The external supplies are...

Page 12: ...e due to electrostatic discharge Electrostatic discharge can damage components Ensure against discharge before touching the product e g by touching an earthed conductive sur face or by wearing an eart...

Page 13: ...e modules with cage clamp terminals All contacts should be protected from contamination The mechanics of the base modules are designed for 50 plug in out cycles Procedure We recommend that you wire up...

Page 14: ...y only be inserted and removed when the load is switched off Unforeseeable error reactions may be triggered if modules are inserted and removed under load When an electronic module is plugged into a b...

Page 15: ...anual PSSu E PD1 T 21453 EN 04 15 5 3 1 Inserting an electronic module Procedure The electronic module must audibly lock into position 1 Mark the electronic module using the labelling strips 2 Schemat...

Page 16: ...operation The configuration data is re tained when a module is changed Effects System environment A In the event of a potential FS communication error the FS section of the PSSu sys tem and all relev...

Page 17: ...0 VDC 48 VAC 48 VAC Use copper wiring The terminal configuration as stated on the front plate applies for base modules without C rail The terminal configuration as stated in the technical documentatio...

Page 18: ...ated 21 11 1 3 2 4 5 6 Please note The minimum cable cross section for field connection terminals on the base modules is 0 14 mm2 AWG26 The maximum cable cross section for field connection terminals i...

Page 19: ...BP 2 16 S PSSu BP 2 16 S T Cage clamp terminals PSSu BP 2 16 C PSSu BP 2 16 C T 11 21 31 41 P1 supply 11 21 31 41 linked intern ally 12 22 32 42 P2 supply 12 22 32 42 linked within the base module 13...

Page 20: ...Operation Operating Manual PSSu E PD1 T 21453 EN 04 20 7 Operation 7 1 Messages and display elements The module provides no diagnostic data and has no display elements...

Page 21: ...ity EN 60068 2 1 EN 60068 2 14 EN 60068 2 2 EN 60068 2 30 EN 60068 2 78 EN 60068 2 1 EN 60068 2 14 EN 60068 2 2 EN 60068 2 30 EN 60068 2 78 Ambient temperature In accordance with the standard EN 60068...

Page 22: ...m 5000 m Airgap creepage In accordance with the standard EN 60664 1 EN 60664 1 Overvoltage category II II Pollution degree 2 2 Protection type In accordance with the standard EN 60529 EN 60529 Mounti...

Page 23: ...PSSu BP 2 16 S T Base module without C rail with screw terminals T type 314 628 PSSu BP 2 16 C Base module without C rail with cage clamp terminals 312 629 PSSu BP 2 16 C T Base module without C rail...

Page 24: ...T p ThE SPIrIT Of SAfETY are registered and protected trademarks of Pilz Gmbh Co KG in some countries We would point out that product features may vary from the details stated in this document dependi...