T H E M O D E R N M - B U S T E C H N O L O G Y
PiiGAB Process Information i Göteborg AB
20
81
0M
.E
.1
.1
4
4.4
Configuration parameters
From the next part in the main menu,
Change Device Parameters
,
configuration of the gateway can be made. This is done to make necessary
adjustments to make the right communication towards the superior system and
towards the meters on the M-Bus loop possible.
Figure 4-10. Change device parameters
At this point there are two choices, to configure the gateway via the network, or
via the serial-port on the gateway. If the serial port is chosen adapter 2 is used,
see chapter 2.8.1. Follow the Wizard instructions to configure via the serial-port.
The difference from configure via the network is that you have to turn the voltage
off and on to get to the installations.
Figure 4-11. Change device parameters