phytron
25
MA 1235-A016 EN
6 Installation
6.1 Mechanical Installation
DANGER
Danger of electric shock in case of foreign particles or damage!
Make sure during the installation that not fixed particles, such as pieces of wire
or assembly parts, can fall into the device. Conductive foreign materials in the
product can endanger persons in case of parasitic voltage and destroy the
device by short circuit.
Rail or Wall Mounting
•
The controller should be vertically mounted.
•
Mount the controller to a plane surface with appropriate load capacity.
•
The wall mounting brackets on two sides of the device allow different mounting
positions.
•
The rail mounting clip is fixed with screws on the rear side.
•
The rap holes can also be used for individual mounting solutions on the rear side.
The mounting screws used must intrude not more than 1 mm into the
device's inner parts (housing thickness: 4mm).
•
Minimum free space above and below the controller: 100 mm
Keep the air slots free to allow convective air exchange.
•
Minimum free space to other devices besides the controller: 30 mm
•
Recommended free space before the controller for connectors and cables: about
35 mm.
•
The heated air flow from other devices and components doesn’t result in
excessive heating of the cooling air.
•
The controller has to be mounted and operated at a place free of shocks and
vibrations.