57
Chapter 7: Programming
To display the current input names, values, and status, type
show inputs
after an ISACC
prompt:
ISACC>
show inputs
INPUT NAME VALUE STATUS LOW LIMIT HIGH LIMIT MIN MAX
IN01 = "Input #1 " = Open OK
IN02 = "Input #2 " = Open OK
IN03 = "Input #3 " = Open OK
IN04 = "Input #4 " = Open OK
IN05 = "Input #5 " = Open OK
IN06 = "Input #6 " = Open OK
IN07 = "Input #7 " = Open OK
IN08 = "Input #8 " = Open OK
IN09 = "Input #9 " = Open OK
IN10 = "Input #10 " = Open OK
IN11 = "Input #11 " = Open OK
IN12 = "Input #12 " = Open OK
IN13 = "Input #13 " = Open OK
IN14 = "Input #14 " = Open OK
IN15 = "Input #15 " = Open OK
IN16 = "Input #16 " = Open OK
ITYPE
This command allows you to program the input type for each of the 16 inputs and assign a
descriptive name. NOTE: The input type programmed must correspond with the shunt
configuration on the ISACC circuit board. See Chapter 4: Inputs. The input types are:
00=Digital: Normally Closed
07=Analog: 10K F
01=Digital: Normally Open
08=Analog: 10K C
02=Digital: Pulse Count
09=Analog: Table 1
03=Analog: 4-20mA
10=Analog: Table 2
04=Analog: 0-5 Volts
11=Analog: Table 3
05=Analog: 2.8K F
12=Analog: Table 4
06=Analog: 2.8K C
13=User Defined
Input type 13 - User defined. The value for an input defined as type 13 is not received from a
physical input but is generated from a C program. See SET_INPUT, Chapter 8.
To display the current input type and name, type
show itype
after an ISACC prompt. You
may also display a specific itype by typing
show itype
followed by the number of the input.
ISACC>
show itype
INPUT TYPE
IN01 is now Digital: N.O.
Name = "Input #1
"
IN02 is now Digital: N.O.
Name = "Input #2
"
IN03 is now Digital: N.O.
Name = "Input #3
"
IN04 is now Digital: N.O.
Name = "Input #4
"
IN05 is now Digital: N.O.
Name = "Input #5
"
IN06 is now Digital: N.O.
Name = "Input #6
"
IN07 is now Digital: N.O.
Name = "Input #7
"
IN08 is now Digital: N.O.
Name = "Input #8
"
IN09 is now Digital: N.O.
Name = "Input #9
"
IN10 is now Digital: N.O.
Name = "Input #10
"
IN11 is now Digital: N.O.
Name = "Input #11
"
IN12 is now Digital: N.O.
Name = "Input #12
"
IN13 is now Digital: N.O.
Name = "Input #13
"
Summary of Contents for Sensaphone ISACC
Page 1: ...Sensaphone ISACC Operator s Manual version 3 49...
Page 22: ...22 Sensaphone ISACC Instruction Manual...
Page 52: ...52 Sensaphone ISACC Instruction Manual...
Page 76: ...76 Sensaphone ISACC Instruction Manual...
Page 114: ...114 Sensaphone ISACC Instruction Manual...
Page 120: ...120 Sensaphone ISACC Instruction Manual...
Page 124: ...124 Sensaphone ISACC Instruction Manual...
Page 130: ...130 Sensaphone ISACC Instruction Manual...
Page 132: ...132 Sensaphone ISACC Instruction Manual...
Page 140: ...140 Sensaphone ISACC Instruction Manual...