32
Sensaphone
®
ISACC Instruction Manual
ISACC units are networked by connecting the
A
terminals together, and the
B
terminals
together. Next, it is necessary to enable a termination on the two units that are located far-
thest apart. This termination is located at pin header P9, located directly above the RS485
terminal block. To enable termination, move the two black jumpers from the off position to
the on position. If only two ISACC units are being networked, enable both. See the follow-
ing diagram:
node 0
node 1
node 3
node 4
node 2
A
B
A
B
A B
A B
A B
Termination
ON
Termination
ON
Five ISACC units networked
After the units are networked, you must determine the node number for each unit. This must
be done so that the each unit is identified in the network. The “master” unit is identified as 0
(zero). See
Chapter 7: PROGRAMMING: “System”
, for information on how to program the
network node number. See
Chapter 7: PROGRAMMING: “Network”
for information on how
to make a network request. See
Chapter 8: C PROGRAMMING
for information on how to
use network information in C programming.
Summary of Contents for Sensaphone ISACC
Page 1: ...Sensaphone ISACC Operator s Manual version 3 49...
Page 22: ...22 Sensaphone ISACC Instruction Manual...
Page 52: ...52 Sensaphone ISACC Instruction Manual...
Page 76: ...76 Sensaphone ISACC Instruction Manual...
Page 114: ...114 Sensaphone ISACC Instruction Manual...
Page 120: ...120 Sensaphone ISACC Instruction Manual...
Page 124: ...124 Sensaphone ISACC Instruction Manual...
Page 130: ...130 Sensaphone ISACC Instruction Manual...
Page 132: ...132 Sensaphone ISACC Instruction Manual...
Page 140: ...140 Sensaphone ISACC Instruction Manual...