MKT-0262 MPC-1748 Rev 02/13
Advanced Pressure Monitor II Rough-In Installation
Wiring
THIS PAGE INTENTIONALLY LEFT BLANK.
Attach pressure tubing as follows:
1. Install the supplied silicone tube (with integrated spring) and attached barbed tube adaptor onto the end of
the 0.25 field tubing. Thread the tubes, with installed adaptor, through the conduit opening at the bottom
of the electrical box.
2. Next push the open end of the soft silicone tubing onto the APM2 pressure tube port labeled "
HIGH
".
3. For the most pressure stable operation, a Pressure Pickup Port installed in the reference pressure area is also
recommended. In this case, install the Pressure Pickup Port in a hallway or reference space.
4. Next push the open end of the soft silicone tubing onto the APM2 pressure tube port labeled "
LOW
".
1.5 Wiring
Figure 1-5.
Rear View of the APM2 (BACnet)
S
howing Wiring and Plum
b
ing Connections
ANALO
G
(ANL) OUTPUT
COM
COM
mA
Current Output (4-20 mA)
Vdc
Voltage Output (0-5 Vdc, 0-10 Vdc)
INPUTS (w
i
red to door N.O.
c
ont
ac
t)
COM
COM
Door
DI
Digital Input
COM
COM
Analog Input2
IN2
Analog Input2 (0-5, 0-10Vdc)
+15
15
Vdc
COM
COM
Analog Input1
IN1
Analog Input1 (0-5, 0-10Vdc)
+15
15 Vdc
Earth Ground
L1
24
Vac
L2
24
Vac
HI
G
H
or
room
pressure tubing
contacts here
LOW
or
referen
c
e
pressure tubing
connects here
POWER
RELAY
COM
COM
+15
+15 Vdc
NO
Normally Open
RC
Relay COM
NC
Normally Closed
COM BACnet APM2-xx-EN
G
-BAC Produ
c
ts
B (+)
A (-)
GND
REAR VIEW