background image

5

www.UsePhoenix.com • [email protected]

Toll-Free 1-800-533-7533

The mixture of gas and liquid refrigerant enter the 

accumulator after leaving the evaporator coil. The 

accumulator prevents any liquid refrigerant from reaching the 

compressor. The compressor evacuates the cool refrigerant 

gas from the accumulator and compresses it to a high 

pressure and temperature to repeat the process.

4.3 Troubleshooting

No dehumidification, neither blower nor compressor run and 

power switch does not light when ON.

1.  Unit unplugged or no power to outlet.
2.  Power switch defective (Sec. 2.6).
3.  Loose connection in internal wiring (Fig. 3).

No dehumidification, neither blower nor compressor run 

with power switch ON & lit.

1.  Low pressure control open (Sec. 2.10).
2.  Power switch defective (Sec. 2.6).
3.  Loose connection in internal wiring (Fig. 3).

Some dehumidification, blower runs continuously but 

compressor only runs sporadically.

1.  Unit is in defrost cycle (Sec. 2.9 & 4.7).
2.  Defrost thermostat defective or loose (Sec. 2.9 & 4.7).
3.  Loose connection in compressor circuit (see Fig. 3).
4.  Defective compressor overload (Sec. 4.6A).
5.  Defective compressor (Sec. 4.6).
6.  Defective relay (Sec. 4.10).

No dehumidification, blower runs but compressor does not.

1.  Bad connection in compressor circuit (Fig. 3).
2.  Pump safety switch closed
2.  Defective compressor capacitor (Sec. 4.6A).
3.  Defective compressor overload (Sec. 4.6A).
4.  Defective compressor (Sec. 4.6).
5.  Defective relay (Sec. 4.10).

Blower does not run. Compressor runs briefly but cycles on 

& off.

1.  Loose connection in blower circuit (see Fig. 3).
2.  Obstruction prevents impeller rotation.
3.  Defective blower (Sec. 4.5).

Unit removes some water but not as much as expected.

1.  Air temperature and/or humidity have dropped.
2.  Humidity meter and/or thermometer used are out of 

calibration.

3.  Unit has entered defrost cycle (Sec. 2.9 & 4.7).
4.  Air filter dirty (Sec. 3.1).

5.  Defective defrost thermostat (Sec. 4.7)
6.  Low refrigerant charge (Sec. 4.4).
7.  Air leak such as loose front cover.
8.  Defective compressor (Sec. 4.6).
9.  Restrictive exhaust ducting (Sec. 2.5)

Unit runs but does not pump water.

1.  Hose kinked or plugged.
2.  Pump motor or float switch defective (Sec. 4.8).
3.  Pump check valve plugged (Sec. 4.8).
4.  Bad connection in pump circuit (Fig. 3).
5.  Hose disconnected internally.

Unit pumps water automatically but not when purge switch 

is pushed.

1.  Bad connection in purge switch circuit (Fig. 3).
2.  Defective purge switch (Sec. 2.7).

Evaporator coil frosted continuously, low dehumidifying 

capacity.

1.  Defrost thermostat loose or defective (Sec. 2.9 & 4.7).
2.  Defrost timer defective (Sec. 2.9 & 4.7).
2.  Low refrigerant charge (Sec. 4.4).
3.  Dirty air filter or air flow restricted. (Sec. 3.1).

Compressor runs with power switch OFF.

1.  Defective relay (Sec. 4.10).
2.  Defective power switch (Sec. 2.6)

4.4 Refrigerant Charging

If the refrigerant charge is lost due to service or a leak, a 

new charge must be accurately weighed in. If any of the 

old charge is left in the system, it must be removed before 

weighing in the new charge. Refer to the unit nameplate for 

the correct charge weight and refrigerant type.

4.5 Blower Replacement

The centrifugal blower has a PSC motor and internal thermal 

overload protection. If defective, the complete assembly must 

be replaced.
1.  Unplug the power cord.
2.  Remove the top panel and cabinet front (6 screws).
3.  Disconnect the blower leads.
4.  Remove the four screws holding the blower outlet flange 

to the cabinet end.

Summary of Contents for 200 MAX

Page 1: ...rying areas to much lower humidity levels than conventional dehumidifiers The Phoenix 200 MAX an improved version of the original Phoenix 200 is the culmination of over a decade of LGR manufacturing and design expertise The Phoenix 200 MAX LGR High Capacity Dehumidifier Improved water removal 16 gals day 128 pints AHAM 80ºF 60 30 gals day maximum Improved grain depression The driest air from an LG...

Page 2: ... GROUND FAULT INTERRUPTER DO NOT use the Phoenix 200 MAX as a bench or table It must always be used in the upright position Read the operation and maintenance instructions carefully before using this unit Proper adherence to these instructions is essential to obtain maximum benefit from your Phoenix 200 MAX dehumidifier Table of Contents Introduction 1 1 Specifications 2 2 Operation 2 2 1 Transpor...

Page 3: ...ditions until the switch is turned off there is no dehumidistat If the unit is going to run for more than 2 hours in an area below 50 F the defrost timer should be adjusted to improve performance see Sec 2 9 2 7 Pump Purge Switch This switch left of hour meter minimizes the water left in the condensate pump reservoir for moving or storage Pressing and holding the pump purge switch will cause the c...

Page 4: ...a drain 2 Plug in the unit but do not turn it on 3 Remove the air filter Slowly pour a quart of the chemical through the heat exchanger 4 Hold in the pump purge switch to reduce the water level in the reservoir 5 Flush with water 4 Service CAUTION Servicing the Phoenix 200 MAX with its high pressure refrigerant system and high voltage circuitry presents a health hazard which could result in death ...

Page 5: ...ive blower Sec 4 5 Unit removes some water but not as much as expected 1 Air temperature and or humidity have dropped 2 Humidity meter and or thermometer used are out of calibration 3 Unit has entered defrost cycle Sec 2 9 4 7 4 Air filter dirty Sec 3 1 5 Defective defrost thermostat Sec 4 7 6 Low refrigerant charge Sec 4 4 7 Air leak such as loose front cover 8 Defective compressor Sec 4 6 9 Rest...

Page 6: ... replaced if continuity exists across its terminals If there is no needle movement with the meter set on the Rx100000 scale the capacitor is open and must be replaced 10 Reconnect the wires to the compressor and capacitor plug in and turn on the unit If the compressor fails to start replace the run capacitor 11 If the unit still does not start adding a hard start kit will provide greater starting ...

Page 7: ...ormation on the evaporator coil the thermostat opens The compressor is then cycled off and on by the defrost timer The blower will continue to run causing air to flow through the evaporator coil and melt the ice when the compressor is off When the air temperature and or humidity increase the evaporator temperature will rise and the thermostat will close to end the defrost cycle 4 8 Condensate Pump...

Page 8: ... of 200 MAX 6 Wiring Diagram 5 Options and Accessories 4021475 16 x 20 x 2 Pleated Media 65 MERV 11 Standardl 4022489 4 Mini Pleat Media 95 MERV 14 Optional 4024750 12 x 25 Intake Flex Duct 4024935 10 x 250 Lay flat Duct 4026600 Phoenix Solution LGR Performance Amplifier 4026734 Phoenix Shield Kit ...

Page 9: ...918 1 Instruction Label 15 4029508 1 Low Pressure Control 16 4021796 1 Pump Purge Switch Item Part No Qty Description 17 4021822 1 Power Switch 18 4029266 1 Top 19 1 Wheel Axle Assembly 4026304 2 Wheel 12 4027125 1 Axle 1284404 2 Cotter Pin 20 4024078 1 Wire Duct Collar Exhaust 21 4025043 1 Skid Panel Items listed below are not shown 22 4023649 1 Condensate Pump 23 4028226 1 Condenser Coil 24 4024...

Page 10: ...e for normal care This warranty does not cover any defect malfunction etc resulting from misuse abuse lack of normal care corrosion freezing tampering modification unauthorized or improper repair or installation accident acts of nature or any other cause beyond Therma Stor LLC reasonable control Limitations and Exclusions If any Phoenix 200 MAX Dehumidifier part is repaired or replaced the new par...

Reviews: