Cabinet Divider 

and Seals

Reactivation Air Outlet

Process Air Inlet

Heater

Principle of Operation

Process Air Outlet

Desiccant Wheel

Desiccant Wheel

Drive and Chain

3 Installation Instructions

Proper installation of this dehumidifier is very important for 
maximum service and performance. Refer to “Installation 
Instructions for the Phoenix 1200 Dehumidifier” label on top 
of machine above control panel.

3.1 Inspection

Thoroughly inspect the dehumidifier inside and out to insure 
that no damage has occurred during shipping. (If any damage 
is found, a claim should be made to the shipping company 
immediately).

3.2 Placing The Machine

Remove any external packaging or crating. 

Note: The supplied casters are stored in the process outlet 
plenum for shipping. Remove and install casters prior to 
operating machine. The dehumidifier should be carefully set 
in place before connecting hose ducts.

3.3 Electrical

All local and state codes must be strictly adhered to and good 
electrical practices should be followed to achieve the best 
installation possible. The supplied power cord must have a 
proper plug or connection as required. Overload protection 
should be sized for 40 amps @220/1/60.

(See Electrical Schematic drawing in the back of this manual 
for internal wiring).

The power supply should be checked to be certain that the 
supply voltage agrees with the equipment nameplate. Serious 
damage to motors and controls can occur if incorrect voltage 
is applied.

3.4 Duct Work

The duct work requirements for these systems are much 
more critical than conventional air conditioning systems. 
ALL SUPPLY AND RETURN AIR DUCT HOSES FOR THE 
DEHUMIDIFIER MUST BE AIR AND VAPOR TIGHT. This is 
extremely important for proper dehumidifier performance. 
Even though the dehumidifier is removing moisture, it may 
not perform properly if moisture enters the dry air stream 
through leaks in the ductwork. The air ducts must be properly 
sized to keep pressure losses at a minimum, and prevent 
this loss from exceeding the designed fan static capability. 
It is important to insure that the reactivation discharge 
air does not enter the process or reactivation inlets. See 
“Specifications” drawing for fan external static pressure.

4 Operating Instructions

Refer to “Installation Instructions for Phoenix 1200 
Dehumidifier” label on top of machine above control panel.
The Phoenix 1200 dehumidifier comes complete ready for 
operation. All that is required is to provide the proper power 
source and duct connections.

4.1 Airflow

The dehumidifier uses two distinct air streams. This 
eliminates the requirement to “balance” the air streams.

4.2 Desiccant Wheel Rotation

A fixed speed gear motor, timing pulley, and timing belt rotate 
the desiccant rotor at the proper speed. The belt tension is 
maintained with a spring loaded roller type tensioner.

5 Start-Up

At this point it is assumed that the installation is complete 
and that the recommendations and instructions have been 
followed. The following will outline the proper procedures for 
starting and adjusting the dehumidifier.

5.1 Manual Operation

If the dehumidifier is to be run continuously, without the use 
of the installed automatic humidistat, place the “HAND/OFF/
AUTO” switch into the “HAND” position. The unit will energize, 
as indicated by the green “UNIT RUN” light, and commence 
dehumidification.

5.2 Automatic Operation

If the dehumidifier is to be operated by the installed 
humidistat, adjust the humidistat to the desired set point, and 
place the “HAND/OFF/AUTO” switch into the “AUTO” position. 
Provided that sensed relative humidity requires dehumidifier 
operation, the unit will energize, as indicated by the green 
“UNIT RUN” light, and commence dehumidification.

Summary of Contents for 1200

Page 1: ... easy lifting External filters and fuses for simple maintenance Tough weather resistant design Operating Range 10ºF to 120ºF Specifications subject to change without notice TS 449b 02 12 4201 Lien Rd Madison WI 53704 PN 4028000 The Phoenix 1200 Portable Desiccant Dehumidifier offers the finest in air drying equipment however this machine can only provide maximum service if properly installed opera...

Page 2: ...hip of the seals and airflow pattern The dehumidifier is designed with the two air streams flowing in opposite directions counter flow thereby maximizing the energy efficiency of the equipment Table of Contents Introduction 1 1 Specifications 2 2 Operation 2 3 Installation Instructions 3 3 1 Inspection 3 3 2 Placing The Machine 3 3 3 Electrical 3 3 4 Duct Work 3 4 Operating Instructions 3 4 1 Airf...

Page 3: ...per dehumidifier performance Even though the dehumidifier is removing moisture it may not perform properly if moisture enters the dry air stream through leaks in the ductwork The air ducts must be properly sized to keep pressure losses at a minimum and prevent this loss from exceeding the designed fan static capability It is important to insure that the reactivation discharge air does not enter th...

Page 4: ...rnal control device specifications for compatibility with the dehumidifier 6 5 Electric Reactivation Controls The dehumidifier is equipped with Positive Temperature Coefficient PTC electric reactivation heaters These heaters are self regulating and require no over temperature safety devices or other electrical controls 7 Dehumidifier Maintenance Instructions 7 1 General Maintenance A definitive ti...

Page 5: ...g contact with chemicals will greatly improve the life of the desiccant Inspect the face of the media to see that no surface damage has occurred If damage is noticed please contact Phoenix for assistance The rotor should turn smoothly upon the shaft if not check the support bearings 9 Dehumidifier Service Instructions 9 1 Removing Desiccant Rotor Desiccant rotor removal is accomplished as follows ...

Page 6: ...r handling equip Seal leaks controlled space outside controlled space 3 Access openings to space not sealed Close and or seal 4 Space not vapor tight Seal with paint and or vapor barrier Faulty humidity controls 1 Humidstat a Improper adjustment a Readjust b Defective b Replace Inadequate air flow 1 Excessive static pressure loss a Dirty filter a Clean or replace b Obstruction at inlet outlet or d...

Page 7: ...amp 1 1 4028128 Relay 4 4028306 Reactivation Heater 6 4028307 Fan Motor 1 4028308 System Fan 1 4028309 Motor Pulley 1 4028144 Fan Pulley 1 4028143 Fan Belt 1 4028310 Rotor Drive Motor kit 1 4029717 Rotor Timing Drive Pulley 1 4028312 Drive Belt 1 4028313 Rotor Seal Divider Seal 16 ft 4026779 Desiccant Rotor 1 4028316 Process Filter 1 4020550 Caster 4 4028317 Power Cord 20 ft 4028318 7 www UsePhoen...

Page 8: ...8 www UsePhoenix com sales UsePhoenix com Toll Free 1 800 533 7533 11 Wiring Diagram ...

Page 9: ...yond Therma Stor Products reasonable control Limitations and Exclusions If any Phoenix 1200 part is repaired or replaced the new part shall be warranted for only the remainder of the original warranty period applicable thereto but all warranty periods will be extended by the period of time if any that the Phoenix 1200 is out of service while awaiting covered warranty service UPON THE EXPIRATION OF...

Reviews: