background image

10 Service Parts

 
Description  

Qty  

Part Number

Disconnect Switch   

1  

 

4028301

Control Switch   

1  

 

4028302

High/Low Switch   

1  

 

4028303

Humidistat   

1  

 

4028126

Humidistat Knob  

 

4028127

Fuse   

8  

 

1932035

Fuse Holder   

8  

 

4028304

Control Transformer  

1 1  

 

4027307

Indicator Lamp  

1 1  

 

4028128

Relay   

4  

 

4028306

Reactivation Heater  

6  

 

4028307

Fan Motor   

1  

 

4028308

System Fan   

1  

 

4028309

Motor Pulley   

1  

 

4028144

Fan Pulley   

1  

 

4028143

Fan Belt   

1  

 

4028310

Rotor Drive Motor kit 

1  

 

4029717

Rotor Timing Drive Pulley   

1  

 

4028312

Drive Belt   

1  

 

4028313

Rotor Seal, Divider Seal   

16 ft. 

 

4026779 

Desiccant Rotor   

1  

 

4028316

Process Filter   

1  

 

4020550

Caster   

4  

 

4028317

Power Cord 

20 ft. 

 

4028318

7

www.UsePhoenix.com • [email protected]

Toll-Free 1-800-533-7533

Summary of Contents for 1200

Page 1: ... easy lifting External filters and fuses for simple maintenance Tough weather resistant design Operating Range 10ºF to 120ºF Specifications subject to change without notice TS 449b 02 12 4201 Lien Rd Madison WI 53704 PN 4028000 The Phoenix 1200 Portable Desiccant Dehumidifier offers the finest in air drying equipment however this machine can only provide maximum service if properly installed opera...

Page 2: ...hip of the seals and airflow pattern The dehumidifier is designed with the two air streams flowing in opposite directions counter flow thereby maximizing the energy efficiency of the equipment Table of Contents Introduction 1 1 Specifications 2 2 Operation 2 3 Installation Instructions 3 3 1 Inspection 3 3 2 Placing The Machine 3 3 3 Electrical 3 3 4 Duct Work 3 4 Operating Instructions 3 4 1 Airf...

Page 3: ...per dehumidifier performance Even though the dehumidifier is removing moisture it may not perform properly if moisture enters the dry air stream through leaks in the ductwork The air ducts must be properly sized to keep pressure losses at a minimum and prevent this loss from exceeding the designed fan static capability It is important to insure that the reactivation discharge air does not enter th...

Page 4: ...rnal control device specifications for compatibility with the dehumidifier 6 5 Electric Reactivation Controls The dehumidifier is equipped with Positive Temperature Coefficient PTC electric reactivation heaters These heaters are self regulating and require no over temperature safety devices or other electrical controls 7 Dehumidifier Maintenance Instructions 7 1 General Maintenance A definitive ti...

Page 5: ...g contact with chemicals will greatly improve the life of the desiccant Inspect the face of the media to see that no surface damage has occurred If damage is noticed please contact Phoenix for assistance The rotor should turn smoothly upon the shaft if not check the support bearings 9 Dehumidifier Service Instructions 9 1 Removing Desiccant Rotor Desiccant rotor removal is accomplished as follows ...

Page 6: ...r handling equip Seal leaks controlled space outside controlled space 3 Access openings to space not sealed Close and or seal 4 Space not vapor tight Seal with paint and or vapor barrier Faulty humidity controls 1 Humidstat a Improper adjustment a Readjust b Defective b Replace Inadequate air flow 1 Excessive static pressure loss a Dirty filter a Clean or replace b Obstruction at inlet outlet or d...

Page 7: ...amp 1 1 4028128 Relay 4 4028306 Reactivation Heater 6 4028307 Fan Motor 1 4028308 System Fan 1 4028309 Motor Pulley 1 4028144 Fan Pulley 1 4028143 Fan Belt 1 4028310 Rotor Drive Motor kit 1 4029717 Rotor Timing Drive Pulley 1 4028312 Drive Belt 1 4028313 Rotor Seal Divider Seal 16 ft 4026779 Desiccant Rotor 1 4028316 Process Filter 1 4020550 Caster 4 4028317 Power Cord 20 ft 4028318 7 www UsePhoen...

Page 8: ...8 www UsePhoenix com sales UsePhoenix com Toll Free 1 800 533 7533 11 Wiring Diagram ...

Page 9: ...yond Therma Stor Products reasonable control Limitations and Exclusions If any Phoenix 1200 part is repaired or replaced the new part shall be warranted for only the remainder of the original warranty period applicable thereto but all warranty periods will be extended by the period of time if any that the Phoenix 1200 is out of service while awaiting covered warranty service UPON THE EXPIRATION OF...

Reviews: