WP 04T, WP 06T, WP 07T/WS, WP 09T/WS, WP 10T, WP 15T
28
PHOENIX CONTACT
8361_en_02
2.3
Connecting the Device
2.3.1
Supply Voltage
The supply voltage is supplied via pin strip X1. A suitable socket strip is supplied.
Refer to the technical data for the permissible supply voltage of the operating device.
Connector in the operating device: 3 pin pin strip
Use the following procedure to connect the device to the supply voltage:
1.
Strip approx. 30 mm (1.181") off the outer cable sheath and approx. 5 mm (0.197") off
the wires.
Figure 2-20
Preparing the cable
2.
Fit the wires with wire end ferrules and connect the wires to the socket strip.
3.
Plug the socket strip onto pin strip X1.
4.
Secure the socket strip in place with a screw-type locking to prevent it from slipping out.
The device has reverse polarity protection. In case of wrong polarity, the device will not
operate.
This is a protection class I device. For safe operation, safety extra-low voltage (SELV) in
accordance with DIN EN 61131 must be used for the supply voltage.
Table 2-1
Pin assignment supply voltage
Pin
Designation
Function
1
Noiseless ground / functional earth ground (FE)
2
0 V
Supply voltage 0 V (GND)
3
24 V
Supply voltage
24 V
DANGER: Hazardous voltages
Hazardous voltages can exist inside electrical installations that can pose a danger to hu-
mans. Coming in contact with live parts may result in electric shock!
NOTICE: Damage
Cables with finely stranded copper conductors with a minimum cross-section of 0.75 mm²
(18 AWG) and a maximum cross-section of 2.5 mm² (14 AWG) must be used for the sup-
ply voltage.
You must adhere to the following torques at the connector:
Screw connection of terminal blocks: 0.22 Nm (minimal) to 0.25 Nm (maximum)
Screw flange: 0.3 Nm (maximum)
Summary of Contents for WP 04T
Page 1: ...Web Panels with TFT Display User manual UM EN WEB PANELS ...
Page 4: ...WP 04T WP 06T WP 07T WS WP 09T WS WP 10T WP 15T PHOENIX CONTACT ...
Page 6: ...WP 04T WP 06T WP 07T WS WP 09T WS WP 10T WP 15T 6 PHOENIX CONTACT 8361_en_02 6 7 WP 15T 58 ...
Page 11: ...Installation and Commissioning 8361_en_02 PHOENIX CONTACT 11 2 2 1 2 WP 06T Figure 2 3 WP 06T ...
Page 15: ...Installation and Commissioning 8361_en_02 PHOENIX CONTACT 15 2 2 1 6 WP 15T Figure 2 7 WP 15T ...
Page 44: ...WP 04T WP 06T WP 07T WS WP 09T WS WP 10T WP 15T 44 PHOENIX CONTACT 8361_en_02 ...
Page 48: ...WP 04T WP 06T WP 07T WS WP 09T WS WP 10T WP 15T 48 PHOENIX CONTACT 8361_en_02 ...
Page 50: ...WP 04T WP 06T WP 07T WS WP 09T WS WP 10T WP 15T 50 PHOENIX CONTACT 8361_en_02 ...
Page 60: ...WP 04T WP 06T WP 07T WS WP 09T WS WP 10T WP 15T 60 PHOENIX CONTACT 8361_en_02 ...