Ordering Data
Safety Measures
None
Error Messages to the Higher-Level Control or Computer System
None
Air and Creepance Distances (According to EN 50178, VDE 0109, VDE 0110)
Isolating Distance
Clearance
Creepance
Distance
Test Voltage
Relay contact/bus logic
≥
5.5 mm
(0.217 in.)
≥
5.5 mm
(0.217 in.)
4 kV, 50 Hz, 1 min.
Contact/contact
≥
3.1 mm
(0.122 in.)
≥
3.1 mm
(0.122 in.)
1 kV, 50 Hz, 1 min.
Contact/PE
≥
3.1 mm
(0.122 in.)
≥
3.1 mm
(0.122 in.)
1 kV, 50 Hz, 1 min.
Description
Order Designation
Order No.
Terminal with four relay changeover contacts;
including connectors and labeling fields
IB IL 24/230 DOR 4/W-PC-PAC
28 62 18 1
Terminal with four relay changeover contacts
IB IL 24/230 DOR 4/W-PC
28 60 41 3
Connector with seven terminals, spring-cage connection
(gray, w/o color print);
pack of 10
IB IL SCN-8-AC-REL
27 40 29 0
Distance terminals
(isolation of various voltage areas);
pack of 1 set (2 pcs.)
IB IL DOR LV-SET
27 42 64 1
Connector for IB IL DOR LV-SET;
pack of 1 set (2 pcs.)
IB IL DOR LV-PLSET
27 42 66 7
"Configuring and Installing the INTERBUS Inline Product
Range" User Manual
IB IL SYS PRO UM E
27 43 04 8