Page 18
Example 2:
If a tyre is tested for 1 hour at a speed of
180 km/h, the total distance travelled is
180 km.
Instantaneous
Numerical value
Number of
Unscaled result
value display
at the
values
in the totalizer
totaizer input
180,0
3 600
648 000,0
X
Hint:
Since one value is transferred each
second, 3600 values are totalled in an
hour. In order to make full use of the dis-
play range of the totalizer, the expected
result will be displayed with two decimal
digits. The 180.00 km corresponds to
a number of 18 000 at the output of the to-
talizer.
The total scaling of
648 000.0 : 18 000 = 0.027777...
Is carried out by setting the factor = 2.7778
(rounded) and the scale = 0.01.
Unscaled result
total
Number at the
Totalizer
in the totalizer
scaling
output of
display
totalizer
648 000,0
0,027778
18 000
X
5.4.2.1 Setting the decimal point for the totalizer
Menu <–> Selection
max. 3 decimal places
The decimal point has only a visual effect
in the display. It does not influence the
result.
5.4.2.2 Overall scaling for the total value
Global scaling
=
Factor
x
scaling
Max. 999.99
=
9.9999
x
100
Min. 0,00001
=
0,0001
x
0,001
Factor and scale influence only the totalizer.
Setting the factor
Menu <–> Selection
Select digit
Set digit
Conversion into other measuring units can
be carried out with the factor.
press the
key to accept
press the
key to accept
Page 19
Setting the scaling
Menu <–> Selection
100
10
1
0,1
0,01
0,001
5.4.3 Resetting the total value
This setting affects the function of the MP input
Chapter 4.2,
9,
Chapter 5.5.1.5,
22, Chapter 5.5.2.5,
24 , Chapter 6.4,
32 and Chapter 6.5,
32
Menu <–> Selection
➱
Resetting the totalizer value to 0 is not possible
Note: At the MP input a Display Hold signal can be set. The alarm
output can only be reset manually.
Only electrical resetting of the totalizer value (Reset pulse at MP input)
Note: The Display Hold Function is off.
In the Latch Mode the alarm outputs can only be resetted
manually.
Manual Reset to 0, only, using the red key.
Note: At the MP input a Display Hold signal can be set. Resetting
the alarm outputs in Latch Mode is only possible electrically.
Manual Reset with the red key and/or with an electrical pulse at
the MP input.
Note: The Display Hold function is off. If the display function
is selected, the alarm outputs can be reset
electrically.
press the
key to accept the selection
press key
to accept
english