Application manual for PSRclassic and PSRmultifunction, and the modular safety relay system
PHOENIX CONTACT
102597_en_03
5.1.2
PSR-ESD/4x1/30 up to PL c/SIL 1
Single-channel emergency stop monitoring with manual reset
Application example
–
Single-channel emergency stop monitoring
–
Manual reset (A1, S34)
–
Stop category 0
–
Safety level of the example up to PL c (EN ISO 13849-1) and SIL 1 (EN 62061)
Figure 5-3
Single-channel emergency stop monitoring with manual reset
PSR-ESD/4x1/30
Order No.
2981800 with screw connection
2981813 with spring-cage connection
Technical data
–
24 V DC
–
2 undelayed enabling current paths, 2 delayed enabling
current paths
–
Adjustable delay time (0 s … 30 s)
–
Monitored manual start or autostart
–
Basic insulation
–
Cat. 4/PLe in accordance with EN ISO 13849-1, SILCL 3 in
accordance with EN 62061
K5
M
K5
S2
M
(N)
(L1)
L+
S1
A1
S
S
12
11
S
S
21
22
A2
S34
S35
( )
( )
PSR-ESD/4x1/30
( )
( )
13
23
37
14
24
38
47
48
Emergency
stop
Reset
(Clock)
(Clock)
Summary of Contents for 2702924