background image

Connecting Serial Control Cables 

 

DBC1220GL Installation Manual Rev I.docx   

5

 

 
 

                                          

 

 
 
 
 

                                        

 

      
 
 
 

                                     

 

 
 

                  

 

 

Supply Cables 

The  supply  input  terminals  are  located  toward 
the centre of the enclosure and consist of Earth, 
Neutral  and  3  Phases,  which  will  accept  up  to 
35mm

2

 cables.  The supply cables should have 

a capacity of 63A per phase, to allow the device 
to be loaded to its maximum capacity. 
 

Load Cables 

Load  cables  can  be  terminated  on  the  2-way 
Load  terminal  blocks  (two  for  each  channel),  a 
Neutral  link  and  an  Earth  link  located  at  the 
centre  of  the  enclosure.    These  connectors  will 
accept up to 10mm

2

 cables.  

It is important that 

an  individual  output  circuit  is  not  overloaded

.  

Calculate the intended load, and ensure that it is 
below  the  maximum  capacity  of  an  individual 
channel,  which  is  20A.    To  ensure  compliance 
with  interference  standards,  the  load  neutral 
cables  must  be  individually  connected  to  the 
neutral  link  terminals  inside  the  cabinet.   

Never 

use a common neutral at a remote location

 

Load Control Cables 

Load Control cables can be terminated on the 2 
x  12  way  terminal  strips  located  directly  above 
the Load terminals.  The left terminal block is the 
output for 0 to +10V, DSI or DALI if selected by 
software  setup.    Note  that  most  types  of  1-10V 
HF  fluorescent  ballast  control  wiring  is  polarity 
conscious.    The  +  terminal  of  the  ballast 
connects  to  the  left  terminal  block,  and  the  -- 
terminal connects to the right (common) terminal 
block.  DSI ballasts are not polarity conscious. 
 

Emergency Lighting Connections 

Connect Emergency Lighting circuit active to the 
load  side  on  the  circuit  breaker  for  the  relevant 
channel,  as  indicated  by  the  labels  next  to  the 
circuit breakers.  Do not remove any cables that 
may already be terminated at this location. 
 

Energising the Device 

If it is necessary to energise load circuits before 
any  control  cables  are  connected,  it  is 
acceptable  to  replace  the  cover  and  energise 
the  device  immediately,  as  the  default  factory 
programming is to have all channels set to 100% 
output.    If  there  is  no  output  on  any  or  all 
channels, see the troubleshooting section (page 
10).  This device should be de-energised before 
terminating the control and data cables.

  

 

 

 
 

Summary of Contents for dynalite DBC1220GL

Page 1: ...ller Installation Manual contents Warning 2 Hardware Controls 7 Features 2 Troubleshooting 8 Important Safeguards 2 Specification 8 Internal View 3 Mounting 4 Supply Load Cable Connections 5 Connecting Serial Control Cables 6 Supplied by ...

Page 2: ...ils Check Connections Treat this device as a switchboard that has been shipped Tighten all load carrying screw connections as vibrations from transport can cause MCB and terminal block screws to become loose Power Sources This device should only be operated from the type of supply specified on the front panel This device must be earthed Output Circuits The load on a circuit should not exceed the s...

Page 3: ...internal view DBC1220GL Installation Manual Rev I docx 3 For spare parts please call your nearest Dynalite Customer Service Centre and specify DBC1220GL ...

Page 4: ...accommodate 4 fixing screws up to 8mm diameter The DBC1220GL can be fixed to the wall without opening the cabinet or removing covers Make sure no dust or other debris enters the device during installation Do not leave the front cover off for any length of time Excessive dust and dirt can degrade the cooling of the internal components Allow for Cable Entry Supply and load cables enter the enclosure...

Page 5: ...ontrol Cables Load Control cables can be terminated on the 2 x 12 way terminal strips located directly above the Load terminals The left terminal block is the output for 0 to 10V DSI or DALI if selected by software setup Note that most types of 1 10V HF fluorescent ballast control wiring is polarity conscious The terminal of the ballast connects to the left terminal block and the terminal connects...

Page 6: ...ed for GND one pair paralleled for VE and one pair used for DATA and DATA Recommended Cable Colour Coding Green White pair Paralleled for GND Orange White pair Paralleled for VE Blue White pair Blue for DATA White for DATA Brown White pair Spare or for Join The colour coding scheme used is not critical as long as the same scheme is used throughout the installation Serial Cable Connecting Method Th...

Page 7: ... than 2 metres Service LED The Service LED has 3 signalling modes which are useful for troubleshooting Blinking slowly 1Hz Normal Operation Blinking fast 4Hz Network Activity Detected On Fault Service Switch The Service Switch has three functions 1 push Transmit Network ID 3 pushes All Channels 100 Push hold for 4 sec Reboot Top Set This control is not used in Ballast controllers Accessory Module ...

Page 8: ...ballast type Check actual wiring against ballast manufacturer s diagram Check 1 10V DSI DALI cable and settings specification Supply 230V 14 50 60Hz 3 Phase Y at 63A per phase Line Outputs 12 x Switched outputs at 20A per channel total device load 189A Control Outputs 12 x load control outputs selectable to 1 10V DSI or DALI Protection 12 x 20A 6kA single pole thermal magnetic circuit breakers Swi...

Reviews: