background image

9

105.4 Electronics Cabinet Voltage Check

Using  a  digital  volt-ohm  meter,  check  for  correct  nominal  battery  voltage  between  electronics  cabinet  DC  Input  NEG  and  POS  wires. 

 

Refer to table in section 

105.3

 for proper system DC voltage. Voltage reading should be ±10% of system DC voltage.

106. AC Connections

CAUTION:

a.  All Inverter system units contain hazardous AC and DC voltages. Because of these voltages, a qualified electrician must install the 

 

 

Inverter system, AC line service, and batteries. The electrician must install the AC line service according to local, state and NEC codes 

 

 

and must be familiar with batteries and battery installation. 

b.   Before  installing,  maintaining,  or  servicing  the  unit,  always  remove  or  shut  off  all  sources  of  AC  and  DC  power  and  shut  off  the 

 

 

Inverter system. Disconnect AC line input at the service panel and turn off the Main DC Switch and the Main AC Switch to make sure

 

  

the unit will not supply output voltage. 

c.  Whenever AC and/or DC voltage is applied, there will be AC voltage inside the  Inverter system unit; the unit can supply  

 

 

power from AC line or from its batteries. To avoid equipment damage or personal injury, always assume that there may be voltage inside 

 

 

the  Inverter system. 

d.  Remove rings, watches, and other jewelry before installing the AC wiring. Always wear protective clothing and eye protection and use 

 

 

insulated  tools  when  working  near  batteries.  Whenever  servicing  an  energized  unit  with  the  inside  panel  open,  electric  shock  is 

 

 

possible; follow all local safety codes. 

TEST BEFORE TOUCHING!

 

e.  To  reduce  the  risk  of  fire  or  electric  shock,  install  the  Inverter  system  and  the  batteries  in  a  temperature-controlled  and 

 

 

humidity-controlled indoor area free of conductive contaminants. See Section 

103

 for operating environment specifications.

 

106.1 AC Wiring Preparations

1.  Remove the system's front cover. Make sure all breakers are in the off position.

2.  Make sure the  Inverter system input and output voltages are correct for the particular application. Remember that the  

 

 Inverter system provides single-phase power only.

3.  The  input  circuit  breaker  in  the  input  service  panel  provides  the  means  for  disconnecting  AC  to  the  Inverter  system. 

 

 

Only authorized persons shall be able to disconnect AC to the unit. (See NEC 700-20 and 700-21.) 

CAUTION:

 To prevent electrical shock  

 

or equipment damage, for all units, the Main AC Switch, the Main DC Switch, all output circuit breakers, and the AC input at the service 

 

 

panel are all off before making AC connections to the  Inverter system.

4.  If  not  previously  done,  remove  knockouts  for  AC  Input  and  AC  Output  in  the  top  or  left  side  of  the  Inverter  system 

 

 

(See 

Fig. 1

 in Section 

104.4

). 

CAUTION:

 Do not drill the cabinet; drill filings may damage the unit and prevent it from operating. If 

 

 

larger knockouts are needed, use a chassis punch to enlarge the appropriate knockout. Do not add additional or unnecessary knockouts.

5.  Install the input and output conduits.

6.  Run  the  AC  Input  service  conductors  and  AC  Output  conductors  through  separate  conduits.  Inverter  system  emergency 

 

 

output  circuits  shall  be  installed  in  dedicated  conduit  systems  and  not  shared  with  other  electrical  circuits  as  described  in  NEC 

 

 

700-9(b).

 

106.2 AC Input and AC Output Connections

 

Make all AC input and output connections to the Inverter system as indicated on the labels within the cabinet.

Circuit Breaker

Access Door

 

 

LED Status

Indicator Panel

Fig. 6

Installer Connections

Building Ground

Line In

Neutral In

Load 2 Neutral Out

Load 1 Neutral Out

AC Output Breaker 2

AC Output Breaker 1

Load 2 Line Out

Load 1 Line Out

Terminal Block 1

Summary of Contents for Bodine ELI-S-600

Page 1: ...ied personnel only 2 Equipment should be mounted in locations and at heights where it will not be readily subjected to tampering by unauthorized personnel 3 The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition 4 Do not use this equipment for other than intended use 5 Do not use outdoors 6 Do not let supply cords touch hot surfaces 7 Do not mount near gas...

Page 2: ...ons 9 105 3 Battery Installation Procedure 9 105 3B Wiring Diagram 3 9 105 4 Electronics Cabinet Voltage Check 9 106 AC Connections 9 106 1 AC Wiring Preparations 10 106 2 AC Input and AC Output Connections 10 107 Final Installation Checklist 10 108 System Start Up Procedure 10 11 109 System Verification 11 Section 200 User Manual Description Page 200 Status Indicators 11 Section 300 Maintenance W...

Page 3: ...verter after a utility power failure 1 ms Battery Battery type Maintenance free sealed lead calcium Battery charger Fully automatic with temperature compensation Recharge time Meets UL requirements 72 Hours Battery protection Automatic low battery voltage disconnect and reverse polarity protection Automatic restart upon utility return Battery switch Also used as battery isolator Standard battery S...

Page 4: ...s in battery storage location because hydrogen is concentrated under the vent cap of each cell of the battery Hydrogen is highly explosive and is hard to detect because it is colorless odorless and lighter than air 103 Installation Requirements 103 1 Operating Environment Install the Inverter system in a clean cool dry place with normal ventilation for human habitation and in such a location to ha...

Page 5: ...l enough to pass through the keyhole K O s provided for mounting This will allow the unit to be hung on partially installed mounting hardware and facilitate easy cabinet removal if ever necessary 104 3 Cabinet Clearance IMPORTANT When mounted the unit requires a minimum of 8 inches 20 3 cm of clearance on both the right and left hand sides of the cabinet to assure proper ventilation 104 4 Knockout...

Page 6: ...g screws or bolts project approximately 1 2 1 3 cm from wall surface Hang sytem cabinet on partially installed hardware and tighten cabinet securely to the wall surface 4 Once the cabinet is securely fastened to the wall run and attach conduit using the provided K O s on the top or left hand side of the unit See Fig 1 Additional entry points if required can be added using a metal punch Do not dril...

Page 7: ...y tools or metal parts on top of the batteries and do not lay any objects where they could fall on to the batteries or into the cabinet 3 Install the batteries as shown on the battery wiring diagram provided in this manual or with the battery cable kit When connecting cables never allow a cable to short across a battery s terminals the string of batteries or to the cabinet 4 Align the cables on th...

Page 8: ...ble IMPORTANT Be careful to observe correct polarity on the battery terminals Illustrations are given as a guide only polarity marking may vary from battery to battery 105 3A WIRING DIAGRAM 1 ELI S 600 72 volt Battery Connection Diagram IMPORTANT Use only Philips Emergency Lighting supplied batteries to assure proper operation and maintain system warranty DO NOT TURN ON THE DC BREAKER AT THIS TIME...

Page 9: ...a free of conductive contaminants See Section 103 for operating environment specifications 106 1 AC Wiring Preparations 1 Remove the system s front cover Make sure all breakers are in the off position 2 Make sure the Inverter system input and output voltages are correct for the particular application Remember that the Inverter system provides single phase power only 3 The input circuit breaker in ...

Page 10: ...d OUTPUT VOLTAGE LEDs should illuminate The OUTPUT CURRENT LED will illuminate only if the emergency lighting fixtures are connected and operable 109 System Verification At this point the connected load should be energized and LED 1 2 and 3 on the unit s status indicator panel should be lit Depending on the state of charge of the batteries the inverter may or may not come on when the test switch i...

Page 11: ...TE To turn power back on follow the System Start up Procedure outlined in Section 108 Be sure to complete all of the steps to as sure the unit will operate properly 300 2 Routine System Maintenance The Inverter unit is designed to provide years of trouble free operation The unit does require some routine attention to assure peak performance Philips Emergency Lighting recommends a Preventative Main...

Page 12: ...r other metal objects and jewelry Don t carry metal objects in pockets where the objects can fall onto the batteries or into the Inverter system or battery cabinet 2 Tools must have insulated handles so that they will not short battery terminals Do not allow a tool to short a battery terminal to another battery terminal or to the cabinet at any time Do not lay tools or metal parts on top of the ba...

Page 13: ... years from the date of shipment Batteries supplied as part of the system are covered under a separate pro rata warranty as described below Batteries 1 year plus 9 years pro rata period 302 Technical Service and Support During or after installation Technical Support is available to provide expert assistance Our service representatives are available to answer customers questions or solve their prob...

Reviews: