Vision.net Ceiling Occupancy Sensor
Installation & Operation Guide
5
Wiring
Ceiling Occupancy Sensors should be connected to an AV Interface Board (63065).
To connect wiring:
Step 1. If conduit is required by local code, route low voltage wiring into adjacent junction
box and secure with included 1/2" nipple.
Step 2. Connect low voltage network to AV Interface Board with (4) #18 AWG wires
according to the wiring diagram below.
Note:
Up to eight (8) Occupancy Sensors may be linked in parallel.
Figure 2: Connecting Low Voltage Wiring
RED (+12VDC)
BLACK (-12VDC GROUND)
WHITE/GREEN (DATA+)
GREEN (DATA -)
J4
1 Black
2 Green
3 White/Green
4 Red
63065 AV Interface Board