Installation & Operation Guide
Vision.net
Ceiling Occupancy Sensor
14
Field/Setting Table:
* Factory Default
To set a Field:
Step 1. After entering the Programming Mode, the Field LED (Blue) will blink one time
(Mode Set), display the present setting (Green blinks), and then repeat the pattern.
Step 2. Each press of the Field Button will select the next Field.
Step 3. Pressing the button after the last field will exit the Programming Mode.
Step 4. Once the Field is selected (proper number of Blue blinks), press the Setting Button
one or more times to change the Field setting. Verify by observing the number of
blinks.
Step 5. You can select the factory default by pressing and holding the Setting Button for 3
seconds.
Notes:
Each tap of the Setting Button will advance the setting by one. Example: Three taps sets the
Field setting to 3 (taps must be less then 2 seconds apart).
After 2 or more seconds following the last tap, the Setting Button will reset back to 1 with the
next tap. Example: Three taps, delay of 2 or more seconds, and then two taps will set the Field
setting to 2.
To set Factory Default for All Fields:
When entering the Programming Mode, instead of holding the Field Button for 3 seconds,
hold it for 10 seconds. After 10 seconds the Sensor will reset the Fields back to Factory
Default, buzz long, and exit the Programming Mode.
Blue Blinks - Field
Green Blinks - Setting
1 - Mode
1 - Aggressive Intelligence
2 - Normal Intelligence
3 - Conservative Intelligence
4- Fixed Timing*
2 - Manual/Automatic
1 - Manual, 2 - Automatic*
3 - Time
1 - 1 min, 2 - 3 min, 3 - 5 min, 4 - 10 min
5 - 15 min*, 6 - 20 min, 7 - 25 min, 8 - 30 min
5 - Sensitivity
1 - Low, 2 - Medium*, 3 - High
6 - Photocell On Sensitivity
1 - Low, ...7 High, 8 - Disabled*