background image

Job Information 

Type:

631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
We reserve the right to change details of design, materials and finish.
www.lightolier.com © 2009 Philips Group • D0609

Architectural Decorative

  4A35

Page 2 of 2 

Pendalux Cirrus 35” Diameter Body 6-26/32/42 Triple Tube

Features

1.  Diffusing Reflector:

 White translucent acrylic, 3/16” thick.

2.  Inner Dirt Shield:

 White translucent acrylic, 1/8” thick.

3.  Chassis:

 Steel, 20 gauge, semi-gloss white powder-coat finish.

4.  Suspension:

 Swivel (central) stem, 5/8” steel tube. Canopy, 7” Dia., 

fastened internally, no exposed hardware. Permits installation on ceilings 
with slope of up to 45˚. Complies with California Code.

5.  Lampholder:

 Multi-wattage, 4-pin, will accept either GX24q-3 or GX24q-4 

lamp base.

Lamping (by others)

Compact Fluorescent:

 Triple Tube, 26, 32, or 42 Watts.

  

General Electric 

Osram/Sylvania 

Philips

26W Triple Tube 4-Pin     (Amalgam) Compact      Fluorescent Lamp
 

F26TBX/*/A/4P 

CF26DT/E/IN/* 

PL-T26W/*/4P

32W Triple Tube 4-Pin     (Amalgam) Compact      Fluorescent Lamp
 

F32TBX/*/A/4P 

CF32DT/E/IN/* 

PL-T32W/*/4P

42W Triple Tube 4-Pin     (Amalgam) Compact      Fluorescent Lamp
 

F42QBK/*/A/4P 

CF42DT/E/IN/* 

PL-T42W/*/4P

*Manufacturers’ color temperature designation.

Electrical

Ballast:

 Electronic, 2-Lamp HPF, Class P, Programmed Start. Universal Voltage 

120/277V, Multi-Wattage 26/32/42W.

6 Lamp

 

26 Watt 

32Watt  

42Watt

Voltage

 

120V   277V  120V   277V  120V   277V

Total Input Watts

 

168 

168 

210 

210 

279 

279

Max. Line Current (amps)

  2.22  0.96  2.80  1.20  1.20  1.60

Power Factor

 

>0.98  >0.98  >0.98  >0.98  >0.99  >0.99

Ballast Factor

 

1.02  1.02 

0.96  0.96  0.95  0.95

THD<10%

  Minimum Starting Temperature: -5°F/-20°C

Mounting

Mounts directly to 4” outlet box, using crossbar hanger, supplied.

Labels

cULus listed suitable for damp locations.

Application Data

Reflectances: 80% Ceiling, 50% Walls, 20% Floor.
Light Loss Factor = .75 (.88 BF x .85)
FC (footcandles) at 30” work plane.

ANGLE  MEAN CP  LUMENS

  655

653  

62

10 

645

15 

632  

179

20 

613

25 

591  

273

30 

566

35 

534  

334

40 

493

45 

451  

349

50 

406

55 

361  

324

60 

315

65 

  268  

267

70 

  226

75 

  184  

196

80 

  146

85 

  110  

124

90 

    90  

      

CERTIFIED TEST REPORT NO. 4A35642A    

COMPUTED BY LSI PROGRAM **TEST-LITE**

LIGHTOLIER INDIRECT/DIRECT PENDANT FIXTURE                 

CAT. #4A353642APBU, 35” DIFFUSER              

6-42W T/E SYLVANIA LAMPS. LUMEN RATING = 3200 LMS.                

3-ADVANCE BALLAST #ICF-2S42-M2-LD, 120 VAC

TESTED ACCORDING TO IES PROCEDURES.  TEST DISTANCE EXCEEDS FIVE 

TIMES THE GREATEST LUMINOUS OPENING OF LUMINAIRE.

ZONE 

LUMENS % LAMP %LUMINAIRE

0-30 

514   

2.68 

3.29

0-40 

848   

4.42 

 

5.42

0-60 

1520   

7.92 

 

9.72

0-90 

2107   

10.98 

 

13.47

40-90 

1259   

6.56 

 

8.05

60-90 

587   

3.06 

 

3.75

90-180 

13538 

70.51 

 

86.53

0-180 

15646   

81.49 

 

100.00

**  EFFICIENCY = 81.5%  **

ANGLE  MEAN CP  LUMENS

90 

90

95 

280  

422

100 

896

105 

1385  

1435

110 

1760

115 

2112  

2095

120 

2458

125 

2759  

2453

130 

2960

135 

3096  

2391

140 

3197

145 

3262  

2045

150 

3303

155 

3356  

1548

160 

3367

165 

3147  

  882

170 

2778

175 

2734  

  268

180 

2972 

C

ANDLEPOWER SUMMARY

ZONAL LUMENS AND PERCENTAGES

DATE: DEC. 14, 2000
PREPARED FOR:
LIGHTOLIER, FALL RIVER, MA

ROOM

 CA

VITY

 RA

TIO

            COEFFICIENTS OF UTILIZATION ZONAL CAVITY METHOD

                   %EFFECTIVE FLOOR CAVITY REFLECTANCE = .20

 

80 

70 

50 

30 

10

 

50  30  10     50  30  10   50  30  10   50  30  10   50  30  10    0 

  1 

.69 .66 .64  .61 .58 .55  .45 .43 .42  .30 .29 .28  .16 .16 .15  .08

 

  2 

.60 .56 .52  .53 .49 .46  .39 .36 .34  .26 .24 .23  .14 .13 .13  .07

 

  3 

.53 .48 .43  .47 .42 .38  .34 .31 .29  .23 .21 .20  .12 .11 .11  .06

 

  4 

.47 .41 .36  .41 .36 .32  .30 .27 .24  .20 .18 .17  .11 .10 .09  .05

 

  5 

.41 .35 .31  .37 .31 .27  .27 .23 .21  .18 .16 .14  .10 .09 .08  .04

 

  6 

.37 .31 .26  .33 .27 .23  .24 .21 .18  .16 .14 .12  .09 .08 .07  .04

 

  7 

.33 .27 .23  .29 .24 .20  .22 .18 .15  .15 .12 .11  .08 .07 .06  .03

 

  8 

.30 .24 .20  .26 .21 .18  .19 .16 .13  .13 .11 .09  .07 .06 .06  .03

 

  9 

.27 .21 .17  .24 .19 .15  .18 .14 .12  .12 .10 .08  .07 .05 .05  .02

 

 10 

.24 .19 .15  .22 .17 .14  .16 .13 .10  .11 .09 .07  .06 .05 .04  .02

DETERMINED IN ACCORDANCE WITH CURRENT IES PUBLISHED PROCEDURES

35 Inch Diameter
36’ x 36’ x 11’ Space
Luminaire   

Spacing: 12’ x 12’

 

 

Susp. Dist. 35”

6 Lamps 

26W 

32W 

42W

 

TTT 

TTT 

TTT

Illum. (FC) 

33 

44 

58

Maint.
Lum. 

8/1 

8/1 

9/1

Ratio
Watts/ 

1.15 

1.42 

1.94

Sq. Ft.

Reviews: