5. Status Description of the Charger Indicating Light
LED Status
Red
Blue
Continuous
lighting
Fading out Continuous
lighting
Continuous
lighting
Fading out
Green
Stand-by
Charging
Charging
Completed
Warning
Ready for
Charging
6. Installation Instructions
SAFETY REQUIREMENTS
●
Be sure to preview the standard operating procedures (SOP) and ensure local
building and electrical codes are reviewed before installing the AC charger.
●
The AC charger should be installed by a qualified technician according to the
instruction manual and local safety regulations.
●
Use appropriate protection when connecting to the main power distribution cable.
●
Type B, C or D breaker in the upstream panel should be installed, and the rating
current of the breaker should be 40A.
●
Disconnect switch for each ungrounded conductor of ac input shall be provided by
others in accordance with the National Electric Code, ANSI/NFPA 70.
6.1 Service Wiring
●
240V Single-Phase
120V
120V
240V
L1
L2
GND
NEUTRAL
(NOT USED)
CAUTION!
THE EVSE is a single-phase device. Do not
connect all three phases of a three-phase feed.
The two phases used must each measure 120 V to
neutral. Earth ground must be conneced to
neutral at only one point, usually at the breaker
panel.
5