DOOR TIME TABLES – LOW ENERGY
(From A156.19 Table I & II)
Table
I:
Minimum
Opening Time to Backcheck or 80 degrees
, which ever occurs
first,
AND
the Minimum
Closing Time from 90 degrees to Latch-Check or 10
degrees
.
5.5
5.0
4.5
4.5
4.0
48 (1219)
4.5
4.5
4.0
4.0
3.5
42 (1067)
4.0
4.0
3.5
3.5
3.0
36 (914)
3.5
3.0
3.0
3.0
3.0
30 (762)
200 (90.7)
175 (79.4)
150 (68.0)
125 (56.7)
100 (45.4)
TABLE
I
“W” Door Weight in Pounds (kg)
“D” Door Leaf
Width - Inches
(mm)
1 second to full open
1.5 seconds to full open
2 seconds to full open
Backcheck at 80 degrees
Backcheck at 70 degrees
Backcheck at 60 degrees
Time From Backcheck (Open check) to Full-Open Position (TABLE
II
)
TOTAL OPENING TIME = TABLE
I
+ TABLE
II
*Consult ANSI/BHMA A156.19-2007 for exact wording and specifications.