PHD FSC-01 Hardware Manual Download Page 10

The maximum voltage that can be applied to an input terminal is 24 volts DC.
Never apply AC voltage to an input terminal.

If the sensor output goes high at the limit,
choose the program option “closed.” If the
output is low at the limit, select “open.”

Wiring a Mechanical Limit Switch

If the sensor output goes low at the limit,
select the option “closed.” If the output is
open, or high voltage, choose “open.”

Limit Sensors

Some systems use active limit sensors that produce a voltage output rather than a switch or relay
closure. These devices must be wired differently than switches.

Wiring for Sourcing Output

Wiring for Sinking or

Open Collector Output

2200

2200

2200

2200

2200

2200

inside FSC-01

IN/JOG COM

IN1

IN2

IN3

IN4

CWJOG

CCWJOG

Wiring Inputs

The FSC-01 input circuits can be used with sourcing or
sinking signals, 5 to 24 volts. This allows connection to
TTL circuits, PLCs, relays, and mechanical switches.
Because the input circuits are isolated, they require a
source of power. If you are connecting to a TTL circuit
or to a PLC, you should be able to get power from the
PLC or TTL power supply. If you are using relays or
mechanical switches, you can use the FSC-01's built-in
24 volt power supply.

Note: If current is flowing into or out of an FSC-01
input, the logic state of that input is low. If no current is
flowing, or the input is not connected, the logic state is
high.

The diagrams on the following pages show how to
connect the FSC-01 inputs to various devices.

FSC-01

+

5-24

VDC

SUPPLY

-

LIMIT COM

CCW LIMIT

CW LIMIT

FSC-01

switch or relay

(closed=logic low)

IN

24V GND

+24 VDC

IN/JOG COM

Connecting an Input to a Switch or Relay

Use normally open momentary switch to trigger FSC-01 using

 Wait Input

 instruction.

Use single throw switch for parameter selection using 

If Input

 instruction.

Use normally open momentary switch for jogging.

-10-

-11-

Switch Model Number       Output Type   Wire # 1   Wire # 2   Wire # 3

18431-001-02 Ind. Prox

18431-002-02 Ind. Prox

51422-005-02

51422-006-02

55802 or 55822 Reed

55803 or 55823 Hall

55804 or 55824 Hall

62505 or 62515

62506 or 62516

NPN

PNP

NPN

PNP

NPN

PNP

NPN

PNP

NPN

PNP

Brown

Brown

Brown

Brown

Blue

Brown

Brown

Brown

Brown

Brown

Blue

Blue

Blue

Blue

Brown

Blue

Blue

Blue

Blue

Blue

Black

Black

Black

Black

Black

Black

Black

Black

Black

Black

PHD Switch Color Code Cross Reference Chart

If your sensor has an open collector output or
a sinking output, wire it like this:

Other sensors have sourcing outputs. That
means that current can flow out of the sensor
output, but not into it. In that case, wire the
sensor this way:

You can use normally open or normally
closed limit switches. Either way, wire
them as shown here.

CW LIMIT

LIMIT COM

24 VDC
Power
Supply

-

+

PHD FSC-01
Motion Controller

Wire
# 1

24 VDC
Power
Supply

-

+

PHD FSC-01
Motion Controller

Switch Model Number       Output Type   Wire # 1   Wire # 2

62507 or 62517 Reed

PNP

NPN

Brown

Blue

Blue

Brown

PHD Switch Color Code Cross Reference Chart

CW LIMIT

LIMIT COM

CW Limit

 24 VDC

Power

Supply

-

+

PHD FSC-01
Motion Controller

Output

   NPN
Proximity
  Sensor

-

+

Wire # 1

Wire # 2

Wire # 3

Limit Com

In/Jog Com

CW Limit

 24 VDC

Power

Supply

-

+

PHD FSC-01
Motion
Controller

PNP

Limit

Sensor

-

+

Limit Com

2 Wire PNP (Source) Schematic

Wire
# 2

62507/62517

Reed Switch

2 Wire NPN (Sink) Schematic

Wire
# 1

Wire
# 2

62507/62517

Reed Switch

Wire # 1

Output

Wire # 3

Wire # 2

Summary of Contents for FSC-01

Page 1: ...Pages Industrial Park Arnold Sommerfeld Ring 2 Leighton Buzzard Bedfordshire LU7 8TP U K D 52499 Baesweiler GERMANY Phone 01525 853488 Fax 01525 378210 Phone 02401 805 230 Fax 02401 805 232 100 7 99...

Page 2: ...rd 6 Connecting the Step and Direction Outputs 7 Installing the PHD Programmer Software 8 Connecting to the PC 8 Front Panel Stop Button 9 Jogging 9 Limit Switches 9 Wiring a Limit Switch 10 Limit Sen...

Page 3: ...5011A EN 50082 1 1996 EN 50178 1997 and TUV Power Supply Output Voltages Inputs Outputs Microstepping Motion Update Physical Connectors Fuses Agency Approvals Features Powerful flexible easy to use in...

Page 4: ...GND 24 VDC OUT3 OUT3 IN JOG COM IN1 OUT2 OUT2 OUT1 OUT1 CCWJOG IN6 LIMIT COM CW LIMIT CCW LIMIT CWJOG IN5 IN4 IN3 IN2 4 17 Getting Started To use your FSC 01 motor control you will need the following...

Page 5: ...keep dust and liquid out Silicone or latex caulking is okay or you can make your own gasket from a sheet of compliant material like rubber or RTV Connecting to 110 Volts The FSC 01 is set for 110 volt...

Page 6: ...afety always use a three wire power cord on anything with a metal case Depending on where you got your power cord it may have black white and green wires or brown blue green The AC power plug that was...

Page 7: ...inputs that require sinking signals and a common terminal named VOPTO or 5V Common cathode Driver inputs are STEP and DIR requiring sourcing signals and a common terminal named common or ground Wirin...

Page 8: ...ing the Programmer Software for detailed installation instructions Connecting to the PC Locate your computer within 6 feet of the FSC 01 Your FSC 01 was shipped with a black adapter plug It has a tele...

Page 9: ...nnect the IN JOG COM and 24 VDC terminals 2200 2200 inside FSC 01 IN JOG COM 24 VDC 24V GND CWJOG CCWJOG inside FSC 01 LIMIT COM CW LIMIT CCW LIMIT 2200 2200 Connecting an NPN Type Proximity Sensor to...

Page 10: ...ed logic low IN 24V GND 24 VDC IN JOG COM Connecting an Input to a Switch or Relay Use normally open momentary switch to trigger FSC 01 using Wait Input instruction Use single throw switch for paramet...

Page 11: ...ed logic low IN 24V GND 24 VDC IN JOG COM Connecting an Input to a Switch or Relay Use normally open momentary switch to trigger FSC 01 using Wait Input instruction Use single throw switch for paramet...

Page 12: ...nnect the IN JOG COM and 24 VDC terminals 2200 2200 inside FSC 01 IN JOG COM 24 VDC 24V GND CWJOG CCWJOG inside FSC 01 LIMIT COM CW LIMIT CCW LIMIT 2200 2200 Connecting an NPN Type Proximity Sensor to...

Page 13: ...ing the Programmer Software for detailed installation instructions Connecting to the PC Locate your computer within 6 feet of the FSC 01 Your FSC 01 was shipped with a black adapter plug It has a tele...

Page 14: ...inputs that require sinking signals and a common terminal named VOPTO or 5V Common cathode Driver inputs are STEP and DIR requiring sourcing signals and a common terminal named common or ground Wirin...

Page 15: ...afety always use a three wire power cord on anything with a metal case Depending on where you got your power cord it may have black white and green wires or brown blue green The AC power plug that was...

Page 16: ...keep dust and liquid out Silicone or latex caulking is okay or you can make your own gasket from a sheet of compliant material like rubber or RTV Connecting to 110 Volts The FSC 01 is set for 110 volt...

Page 17: ...GND 24 VDC OUT3 OUT3 IN JOG COM IN1 OUT2 OUT2 OUT1 OUT1 CCWJOG IN6 LIMIT COM CW LIMIT CCW LIMIT CWJOG IN5 IN4 IN3 IN2 4 17 Getting Started To use your FSC 01 motor control you will need the following...

Page 18: ...5011A EN 50082 1 1996 EN 50178 1997 and TUV Power Supply Output Voltages Inputs Outputs Microstepping Motion Update Physical Connectors Fuses Agency Approvals Features Powerful flexible easy to use in...

Page 19: ...rd 6 Connecting the Step and Direction Outputs 7 Installing the PHD Programmer Software 8 Connecting to the PC 8 Front Panel Stop Button 9 Jogging 9 Limit Switches 9 Wiring a Limit Switch 10 Limit Sen...

Page 20: ...Pages Industrial Park Arnold Sommerfeld Ring 2 Leighton Buzzard Bedfordshire LU7 8TP U K D 52499 Baesweiler GERMANY Phone 01525 853488 Fax 01525 378210 Phone 02401 805 230 Fax 02401 805 232 100 7 99...

Reviews: