PHCC Pro Series 2200 Instruction Manual & Safety Warnings Download Page 14

this procedure.  The pump is designed to run
dry, so if there is no water in the sump pit
during the test, the pump will not be
damaged.

3. If the control unit still indicates that the

pump is defective, replace the pump.  The
procedure is described in the next column.

Your Pro Series 2200 has a 20-amp DC safety
fuse in the back of the cabinet to protect the
unit and the battery.  If the fuse blows, the
pump alarm will sound to alert you to the
problem.  Replace the 20-amp fuse.  If it blows
again, unplug the computer control unit from
the wall and disconnect the battery cables
from the battery.  Then call Glentronics’ service
department for instructions.

PUMP WAS ACTIVATED

When the water rises in the sump pit and lifts
the float switch, the pump will begin pumping,
and the “Pump was activated” light and alarm
will turn on.  The pump warning stays on to alert
you to the fact that the standby system was used
to empty the water from the sump.  Try to
determine what caused the system to activate.

• Check the main pump for failure.  It may not be

working, the float switch may be stuck, or it
may be too small to handle the inflow of water.

• Make sure the check valve is working and

installed correctly.  It may need to be
replaced.

• Make sure the discharge pipe is not clogged or

frozen.

• If the power was out, and the backup pump

was activated, you need to push the GRAY
button to silence the alarm.

REPLACING THE PUMP

Unplug the main AC pump when installing the
backup pump to avoid electric shock.  Failure
to do so could cause serious injury or death.
Review the safety instructions on page 1.

REFER TO PHOTOS AT RIGHT

1. Unplug the pump from the back of the control

unit.

2. Release the union or check valve and remove

the pump and the rigid PVC pipe section from
the sump pit.

3. Unscrew the pipe and fitting from the old

pump, and screw them into the new pump.

4. Lower the pump into the sump and reconnect

the union or check valve.

5. Plug the pump wires into the back of the

control panel.  

BE SURE TO PLUG IN THE

MAIN AC PUMP.

BATTERY POWER LEVEL

Your Pro Series backup sump pump system has a
gauge which will report the level of charge in the
battery.  As the battery’s energy is depleted
during operation without AC power, or simply by
aging, the gauge will indicate the percent of
charge remaining in the battery.  Should the
percent drop below 25%, the “Battery problem”
indicator will light up and the alarm will sound.

If this warning goes on while the pump is
running, you will have a minimum of 1 hour to
replace the battery.  (In most cases the pump
does not run continuously, and therefore, it will
run much longer.)  In a severe emergency, if a
replacement battery is not available, you could
temporarily use your car battery.

Once the AC power is restored, the battery will
recharge, unless it is old or damaged.  Press the
GRAY button for 1 second to reset the alarm.

Page 13

1

4

3

!

DANGER

LIFT

FLOAT

2

1

2

5

Summary of Contents for Pro Series 2200

Page 1: ...ge to outside 4 Connection to existing discharge 5 Direct discharge for narrow sumps 6 Connection to existing discharge for narrow sumps 7 Battery Instructions 8 Control Unit Connections Positioning t...

Page 2: ...hese risks observe the following precautions Someone should be within range of your voice or close enough to come to your aid when you work near a lead acid battery Have plenty of fresh water and soap...

Page 3: ...ndby Battery or another deep cycle battery 11 2 rigid PVC pipe and fittings PVC cement and primer A union or a Y connector and two 2 check valves depending on the installation method you use Six 6 qua...

Page 4: ...arrow pits the backup pump can be mounted above the main pump Try to fit the backup pump on the floor of the sump first Select the installation method that will best suit your needs from the diagrams...

Page 5: ...to an exterior wall via the shortest path with the fewest turns More turns will reduce the pumping capacity The pipe section exiting the building should be on a downward slope so that the water in the...

Page 6: ...If there is no check valve on the main AC pump one must be installed at this time Then install a Y connector above the check valve on the discharge pipe for the main AC pump 4 Secure the pump wire so...

Page 7: ...rest of the pipe and the details of each installation will vary Using sound plumbing practices try to route the discharge pipe to an exterior wall via the shortest path with the fewest turns More tur...

Page 8: ...the arrow pointing up or it will not prevent the backflow of water 4 b When a check valve is used drill a 1 8 hole in the 11 2 PVC pipe three inches 3 above the connection to the Pro Series pump Drill...

Page 9: ...ention Review the safety instructions on page 1 1 Remove the battery box top by pushing in the tabs on the front and back of the box and lifting up 2 Place the battery box on the floor Place the dry u...

Page 10: ...ile or any incoming rush of water 2 Connecting the pump Remove the security tag from the pump and plug the pump wires into the pump connector on the back of the control unit 3 Installing the battery f...

Page 11: ...protection Work in a well ventilated area Do not smoke or allow a spark or flame in the vicinity of the battery Avoid dropping metal tools on the battery If battery acid contacts eyes flush with water...

Page 12: ...the battery is relatively new and the battery alarm is activated before you replace the battery call the Glentronics service department The phone number is 800 991 0466 option 3 TO CLEAN THE BATTERY T...

Page 13: ...lence the Power failure alarm for 24 hours by pressing the GRAY button for 5 seconds The alarm will be silenced but the light will stay on The system will continue to operate while the power alarm is...

Page 14: ...ush the GRAY button to silence the alarm REPLACING THE PUMP Unplug the main AC pump when installing the backup pump to avoid electric shock Failure to do so could cause serious injury or death Review...

Page 15: ...is broken Backup pump is clogged PUMP WAS Possible Reasons The main AC pump failed because of a power outage The main AC pump is broken The float switch on the main pump is jammed or defective The mai...

Page 16: ...ed as evidence of the date of purchase and to establish warranty eligibility This warranty does not cover product problems resulting from handling liquids hotter than 120 degrees Fahrenheit handling i...

Reviews: