NOTE: Serious Damage To The Burner May Result If The Blast
Tube Is Extended Into The Combustion Chamber.
4.5
Secure the burner to the heat exchanger or boiler, using the burner-mounting flange. The burner-
mounting flange must be secured to the blast tube at the selected location for proper insertion
into the end or front wall of the fired unit. A tight seal between the mounting flange and the front
plate should be accomplished using the factory-furnished gasket or a ceramic or other non-
asbestos fiber rope.
5
GAS PIPING
5.1
Contact you local gas service company to ensure that adequate gas service is available and to
review applicable installation codes for your area. All gas piping installations must be in
accordance with NFPA 54, National Fuel Gas Code, Definitions and General Field
Recommendations, CGA 3.0, Canadian Natural Gas Installation Code CAN/CGA B149.1 or
Propane Installation Code, CGA B 149.2. This product must be installed only by a Licensed
Plumber or Gasfitter, when installed in the Commonwealth of Massachusetts.
5.2
Size the main gas line in accordance with Table 2. The figures shown are for straight lengths of
pipe at 0.2” w.c. pressure drop, which is considered normal for low-pressure systems. Note that
fittings such as elbows and tees will add to the pipe pressure drop.
Table 2 - Gas Piping Pressure Drop Data
EQUIVALENT LENGTH OF STRAIGHT PIPE IN FEET
20
30
40
50
60
80
100
150
200
Pipe Size In Inches
CFH GAS WITH .2” PRESSURE DROP
3/4”
152
120
105
93
84
73
66
54
45
1”
300
250
210
190
180
150
135
110
75
1-1/4”
520
425
360
325
300
260
230
190
165
1-1/2”
800
690
560
500
480
410
370
300
260
2”
1700
1400
1200
1100
1000
850
750
600
540
2-1/2” 3000
2500
2100
1900
1800
1550
1375
1100
950
EQUIVALENT LENGTHS OF STANDARD PIPE IN FEET FOR LISTED FITTINGS
Fitting Type
3/4
1
1-1/2
1-1/2
2
2-1/2
Nominal Pipe Size In Inches
Std. Tee
2.4
5.5
7.5
9.0
12.0
13.5
Std. Elbow
4.4
2.7
3.7
4.5
5.5
6.1
5.3
Refer to Figure 3 for details of gas piping. (Also refer to any additional piping diagrams supplied for this
specific unit.)
5.4
Mount leakage test and main gas cocks, main automatic gas valve or combination gas
valve/pressure regulator, and auxiliary valves (if required and not factory mounted) per piping
diagram or Figure 3.
5.5
Install pressure regulator (not used with combination gas valve/pressure regulator) directly
upstream of main automatic gas valve(s) and fit drip leg and main gas cock upstream of regulator
or automatic valve(s).
5.6
The pilot line should be piped into the upstream tapped nipple to minimize pilot line piping length.
An optional location is in a tapping located on the main shut-off cock. Refer to Figure 3. For
ease of servicing we recommend the use of a union immediately upstream of the main gas
pressure regulator or combination gas valve/pressure regulator.