background image

The torch box exhaust must be installed, but the RF generator 
exhaust is optional (see note in Table 7*).  

The RF generator exhaust vent is used for the blower that 
cools the system power supplies and ICP generator.

We recommend using two 100-mm (4 in.) exhaust hoses  
(for both the torch box exhaust vent and RF generator 
exhaust vent). The NexION 300 ICP-MS is supplied with 6 m 
(22 ft.) of 100-mm (4 in.) flexible tubing. This tubing permits 
the movement of the instrument without disconnecting the 
vents from the laboratory system. See Tables 6 and 7 for 
vent specifications.

In operation, the roughing pump produces 1200-1500W 
(4100-5100 BTU/hr) of heat. The heat from the roughing 
pump is released into the laboratory. Proper ventilation is 
required to remove this heat from the room or any enclosure 
in which the pump is situated. There must be a minimum of 
15 cm (6 in.) clearance between the rear of the pump and 
any vertical surface as well as a minimum of 35 cm (14 in.) 
clearance in the front. It should be located away from other 
heat generating sources such as the liquid cooling system. 
The ambient air temperature must NOT exceed 40 °C at the 
roughing pump control electronics.

The heat from the liquid cooling system (heat exchanger or 
refrigerated chiller) is also released into the laboratory during 
operation. The heat exchanger will produce a maximum of 
2000W (6825 BTU/hr) of heat. The refrigerated chiller will 
produce a maximum of 3000W (10,000 BTU/hr) of heat.  
Proper ventilation is required to remove this heat from the 
room or any enclosure in which the liquid cooling system 
is situated. Adequate clearance should be allowed on the 
front, sides, and rear of the unit for access to connections 
and components. The front and rear vents of the unit must 
be a minimum of 61 cm (2 ft.) away from walls or vertical 
surfaces so air flow is not restricted. It should be installed at 

7

least 1.4 meters (4 ft.) away from any heat-generating 
sources such as the roughing pump or other instruments. 

Proper ventilation is critical for the heat exchanger – its 
ambient air temperature must never exceed 30 ˚C.

Venting System Recommendations

The exhaust flow rate at the instrument (the ability to vent 
the system) is dependent on customer-provided blower, the 
duct length, material and the number of elbows or bends 
used. If an excessively long duct system or a system with 
many bends is used, a stronger blower may be necessary to 
provide sufficient exhaust volume at the instrument. Smooth 
stainless steel tubing should be used instead of flexible stain-
less steel tubing, where flexibility is not required, to reduce 
system friction loss or “drag.” A length of smooth stainless 
steel ducting has 20-30% less friction loss than a comparable 
length of flexible ducting. When smooth stainless steel  
tubing is used, elbows must be used to turn corners. These 
elbows should turn at no more than 45 degrees between 
straight sections to reduce friction losses, and the number  
of elbows should be minimized.

Additional recommendations on the venting system include:

•  The duct casing and venting system should be made of 

materials suitable for temperatures as high as 70 ˚C and 
be installed to meet local building code requirements. 

•  Locate the blower as close to the discharge outlet as possible. 

All joints on the discharge side should be airtight, especially if 
toxic vapors are being carried.

•  Equip the outlet end of the system with a backdraft 

damper and take the necessary precautions to keep the 
exhaust outlet away from open windows or inlet vents 
and to extend it above the roof of the building for proper 
dispersal of the exhaust.

•  Equip the exhaust end of the system with an exhaust 

stack to improve the overall efficiency of the system. 

Table 7.  Hose Diameter and Venting Capabilities.*
Hose 

Hose Diameter 

Heat Vented Outside Lab Watts (BTU/hr)

Torch Box Exhaust 

100 mm (4 in.) 

800 (2720)

RF Generator Exhaust 

100 mm (4 in.) 

1500 (5100)

*If only the Torch Box exhaust hose is used, approximately 1500W (5100 BTU/hr) of heat from the RF generator exhaust is vented into the lab.  

An independent room air conditioner [3000W (10000 BTU/hr)] is recommended to remove this additional heat. 

Table 6.  Instrument Exhaust Ventilation Requirements.
 

Required airflow 

Required air velocity

 

Reference airflow 

Reference air velocity

 

measured with hose connected to NexION

 

measured with hose disconnected from NexION

Torch Box  

Exhaust Port

 

73 – 100 ft

3

/min @ 0.5" H

2

836 – 1145 ft/min @ 0.5" H

2

O

 

110 – 150 cfm @ 0" H

2

1260 – 1719 ft/min @ 0" H

2

O

 

(35 – 47 L/sec @ 125 Pa) 

(4.3 – 5.8 m/sec @ 125 Pa)

 

(52 – 71 L/sec @ 0 Pa) 

(6.4 – 8.7 m/sec @ 0 Pa)

RF Generator  

Exhaust Port

  150 – 160 ft

3

/min @ 0" H

2

O  1719 – 1833 ft/min @ 0" H

2

O

  150 – 160 ft

3

/min @ 0" H

2

O  1719 – 1833 ft/min @ 0" H

2

O

 

(71 – 76 L/sec @ 0 Pa) 

(8.7 – 9.3 m/sec @ 0 Pa)

 

(71 – 76 L/sec @ 0 Pa) 

(8.7 – 9.3 m/sec @ 0 Pa)

Summary of Contents for NexION 300 ICP-MS

Page 1: ...ft above sea level In addition the instrument should be located in an area that is Indoors Free of smoke dust and corrosive fumes Not prone to excessive vibration Out of direct sunlight Away from heat...

Page 2: ...quired In operation NexION can be operated with the back up against a wall Access for most service procedures is through the front of the instrument However some infrequent service procedures may requ...

Page 3: ...cart or table to allow for easy service access The system computer may be placed on the instrument bench or a separate computer table System Layout The ICP MS system consists of the main instrument ro...

Page 4: ...plosive accumulations Move or store gas cylinders only in a vertical position with the valve cap in place Locate gas cylinders away from heat or ignition sources including heat lamps Cylinders have a...

Page 5: ...l for UCT instruments only Cooling Liquid 344 14 kPa 60 2 psig 3 8 L min 1 0 gpm minimum 4 7 L min 1 25 gpm typical 5 Table 4 NexION 300 ICP MS Power Specifications Power Consumption Maximum Volt Ampe...

Page 6: ...5 Pa static pressure when the plasma is off during operation the static pressure drops to zero Both of the exhaust ports should be connected directly to flexible exhaust hoses Use the vent adapter to...

Page 7: ...umber of elbows or bends used If an excessively long duct system or a system with many bends is used a stronger blower may be necessary to provide sufficient exhaust volume at the instrument Smooth st...

Page 8: ...t common cell gases used with the NexION 300 ICP MS are ultra pure helium and anhydrous ammonia For best efficiency make sure the length of the duct that enters into the blower is a straight length at...

Page 9: ...cell gases at the working pressures listed in Table 8 The NexION 300 ICP MS is shipped with the regulator to cylinder fittings shown in Table 8 The cell gas cylinders should use this type of fitting w...

Reviews: